Daikin Microtech III [19/44] Unit capacity control will be performed as described in this section all unit capacity limits described in following sections must be applied as described
- 19 -
8.4.2.2. Auto Control
If auto pump control is selected, the primary/standby logic above is still used. When the evaporator is not in the run
state, the run hours of the pumps will be compared. The pump with the least hours will be designated as the primary
at this time.
8.5. LWT Target
The LWT Target varies based on settings and inputs.
The base LWT Target is selected as follows:
Control Source
Set Point
Mode
Input
BAS
Request
Available Modes
Set Point
Base LWT Target
Local OFF COOL
Cool Set Point 1
Local ON COOL
Cool Set Point 2
Network COOL
BAS Cool Set Point
Local OFF COOL w/Glycol Cool Set Point 1
Local ON COOL w/Glycol Cool Set Point 2
Network COOL w/Glycol BAS Cool Set Point
Local OFF COOL/ICE w/Glycol Cool Set Point 1
Local ON COOL/ICE w/Glycol Ice Set Point
Network COOL COOL/ICE w/Glycol BAS Cool Set Point
Network ICE COOL/ICE w/Glycol BAS Ice Set Point
Local ICE w/Glycol Ice Set Point
Network ICE w/Glycol BAS Ice Set Point
8.5.1. Leaving Water Temperature (LWT) Reset
The base LWT target may be reset if the unit is in Cool mode and LWT reset is enabled via the set point.
The reset amount is adjusted based on the 4 to 20 mA reset input. Reset is 0° if the reset signal is less than or equal
to 4 mA. Reset is 5.56°C (10.0°F) if the reset signal equals or exceeds 20 mA. The amount of reset will vary
linearly between these extremes if the reset signal is between 4 mA and 20 mA.
When the reset amount increases, the Active LWT Target is changed at a rate of 0.1°C every 10 seconds. When the
active reset decreases, the Active LWT Target is changed all at once.
After the reset is applied, the LWT target can never exceed a value of 15.56°C (60°F).
8.6. Unit Capacity Control
Unit capacity control will be performed as described in this section. All unit capacity limits described in following
sections must be applied as described.
8.6.1. Compressor Staging in Cool Mode
The first compressor on the unit is started when evaporator LWT is higher than the Startup Temperature.
Additional compressors can be started when Evaporator LWT is higher than the Stage Up Temperature and the
Stage Up Delay is not active.
When multiple compressors are running, one shut down if evaporator LWT is lower than the Stage Down
Temperature and the Stage Down Delay is not active.
All running compressors shut down when the evaporator LWT is lower than the Shut Down Temperature.
8.6.1.1. Stage Up Delay
A minimum amount of time, defined by the Stage Up Delay set point, passes between increases in the capacity
stage. This delay only apply when at least one compressor is running. If the first compressor starts and quickly
shuts off for some reason, another compressor may start without this minimum time passing.