Daikin Microtech III — управление BACnet и Modbus: Индикация и Обслуживание [43/44]

Daikin Microtech III [43/44] Controller maintenance
- 43 -
Bacnet IP:
BuS LED Mode
Solid Green Ready for Communication. The BACnet Server is started. It
doesn't indicate a active communication
Solid Yellow Startup. The LED stays yellow until the module receives a IP
Address, therefore a link must be established.
Solid Red BACnet Server down. Automatic restart after 3 seconds is
initiated.
Modbus
BuS LED Mode
Solid Green All Communication running
Solid Yellow Startup, or one configured channel not communicating to the
Master.
Solid Red All configured Communications down. Means no
communication to the Master. The timeout can be configured. In
case that the timeout is zero the timeout is disabled.
Controller maintenance
The controller requires to maintain the installed battery. Every two years it’s required to replace the battery.
Battery model is: BR2032 and it is produced by many different vendors.
To replace the battery remove the plastic cover of the controller display using a screw driver as shown in the
following picture:
Be careful to avoid damages to the plastic cover. The new battery shall be placed in the proper battery holder
which is highlighted in the following picture, respecting the polarities indicated into the holder itself.