Daikin Microtech III — настройки тестового режима и конфигурации устройств [15/44]

Daikin Microtech III [15/44] When the unit mode is no longer test all unit test mode set points are be changed back to their off values when test mode is no longer enabled for a circuit all the circuit test mode set points for that circuit are changed back to their off values
- 15 -
The following settings can be automatically set back to Off after being On for 1 second:
Clear Alarms
Network Clear Alarms
Clear Cycle Timers
Clear Ice Timer
Stage Delay Clear
6.2. Test Mode Set Points
All outputs are manually controllable via test mode set points only when test mode is enabled.
For Unit level outputs test mode is enabled only when the unit mode is Test. For Circuit outputs test mode is
enabled when either unit mode is Test, or the circuit mode is Test.
The compressor outputs are a special case, and they are allowed to remain on for 3 seconds before being
automatically set back to ‘off’.
When the unit mode is no longer Test, all unit test mode set points are be changed back to their ‘off’ values. When
test mode is no longer enabled for a circuit, all the circuit test mode set points for that circuit are changed back to
their ‘off’ values.
7. Unit Configurations
The table below summarizes the possible unit configurations:
Number of Fans
Number of
Circuits
Number of
Compressors
Unit Type
4
1
2 “V”
3 “V”
2 2
“V”
5
1
2 “V”
3 “V”
2 2 “V”
6
1
2 “V”
3 “V”
2 2 “V”
3+3 2 2 “W”
4+4 2
2 “W”
3 “W”
5+5 2
2 “W”
3 “W”
6+6 2
2 “W”
3 “W”
“V” type
Condensation is managed at unit level. Both circuits work with the same saturated condensing temperature, more
specifically, with the higher of each circuit probe readings.
“W” type
Condensation is managed at circuit level. Each circuits works with its own saturated condensing temperature.