Edit Mode
The Editing Mode is entered by pressing the navigation wheel while the cursor is pointing to a line containing
an editable field. Once in the edit mode pressing the wheel again causes the editable field to be highlighted.
Turning the wheel clockwise while the editable field is highlighted causes the value to be increased. Turning the
wheel counter-clockwise while the editable field is highlighted causes the value to be decreased. The faster the
wheel is turned the faster the value is increased or decreased. Pressing the wheel again cause the new value to
be saved and the keypad/display to leave the edit mode and return to the navigation mode.
A parameter with an “R” is read only; it is giving a value or description of a condition. An “R/W indicates a
read and/or write opportunity; a value can be read or changed (providing the proper password has been entered).
Example 1: Check Status, for example -is the unit being controlled locally or by an external network? We are
looking for the Unit Control Source Since this a unit status parameter, start at Main Menu and select View/Set
Unit and press the wheel to jump to the next set of menus. There will be an arrow at the right side of the box,
indicating that a jump to the next level is required. Press the wheel to execute the jump.
You will arrive at the Status/ Settings link. There is an arrow indicating that this line is a link to a further menu.
Press the wheel again to jump to the next menu, Unit Status/Settings.
Rotate the wheel to scroll down to Control Source and read the result.
Example 2; Change a Set point, the chilled water set point for example. This parameter is designated as Cool
LWT Set point 1 and is a unit set parameter. From the Main Menu select View/Set Unit. The arrow indicated
that this is link to a further menu.
Press the wheel and jump to the next menu View/Set Unit and use the wheel to scroll down to Temperatures.
This again has an arrow and is a link to a further menu. Press the wheel and jump to the Temperatures menu,
which contains six lines of temperatures set points. Scroll down to Cool LWT 1 and press the wheel to jump to
the item change page. Rotate the wheel to adjust the set point to the desired value. When this is done press the
wheel again to confirm the new value. With the Back button it will be possible to jump back to the
Temperatures menu where the new value will be displayed.
Example 3; Clear an Alarm,. The presence of a new alarm is indicated with a Bell ringing on the top right of
the display. If the Bell is frozen one or more alarm had been acknowledged but are still active. To view the
Alarm menu from the Main Menu scroll down to the Alarms line or simply press the Alarm button on the
display. Note the arrow indicating this line is a link. Press the wheel to jump to the next menu Alarms There
are two lines here; Alarm Active and Alarm Log. Alarms are cleared from the Active Alarm link. Press the
wheel to jump to the next screen. When the Active Alarm list is entered scroll to the item AlmClr which is set to
off by default. Change this value to on to acknowledge the alarms. If the alarms can be cleared then the alarm
counter will display 0 otherwise it will display the number of alarm still active. When the alarms are
acknowledged the Bell on the top right of the display will stop to ring if some of the alarms are still active or
will disappear if all the alarms are cleared.