Daikin EUWAC8FZW [12/26] Capacity tables

Daikin EUWAC8FZW [12/26] Capacity tables
3
1
6
Applied Systems • Chillers
13
Chillers • R-407C • EUWAC-FZW
6 Capacity tables
6 - 1 Cooling capacity tables
3TW55052-1B
SYMBOLS
CC : Cooling capacity (kW)
PI : Power input (kW)
LWE : Leaving Water Evaporator temperature (°C)
Ta : Air suction temperature (°C)
NOTES
1 Cooling capacity (CAP)
Capacity is according to Eurovent rating standard 6/C/003-2003 and
valid for chilled water range Dt = 3 - 8°C.
2 Power input (kW)
Power input is total input according to Eurovent rating standard
6/C/003-2003: Compressor + fans + control circuit.
3 External static pressure
Values for CC and PI are for a nominal ESP, at a factory fan motor pulley
setting of 0 turns open:
5HP ESP 50 Pa
8HP ESP 60 Pa
10 HP ESP 72 Pa
CC-10HP
Ta/LWE
CC - 8 HP
Ta/LWE
Ta/LWE
CC - 5 HP

Содержание

Скачать