Notes Nominal capacities are based on the following conditions: Entering/leaving chilled water temperature: 12°C/7°C
Ambient temperature: 35°C
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value,
depending on the distance and acoustic environment.
The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.
3-2 ELECTRICAL SPECIFICATIONS EUWAC5FZW1 EUWAC8FZW1 EUWAC10FZW1
Power Supply Name W1
Phase 3N~
Frequency Hz 50 50 50
Voltage V 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Unit Starting Current A 81 110 145
Nominal Running Current
Cooling
A 11.30 14.00 16.80
Maximum Running Current A 16.80 21.40 25.50
Recommended fuses according to
IEC standard 269-2
3x25gG 3x32gG 3x32gG
Fan Quantity 1 1 1
Nominal Running Current
Cooling
A 4.60 3.30 3.30
Maximum Running Current A 6.80 3.40 3.50
Starting current (MSC) A 20.7 14.9 14.9
Compressor Phase 3~
Voltage V 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Starting current A 60.0 95.0 130.0
Nominal running current
(RLA)
A 6.70 10.70 13.50
Maximum Running Current A 10.00 18.00 22.00
Starting Method Direct on line
Control Circuit Phase 1~
Voltage V 230V/24V AC (supplied by factory installed performers)
Recommended fuses Factory installed
Crankcase heater (E1/2HC) W 33 50 50
3-1 TECHNICAL SPECIFICATIONS EUWAC5FZW1 EUWAC8FZW1 EUWAC10FZW1