1.3 Operational Range: EWAD110~540MBYNN
Operational range The illustration below shows the operational range of EWAP110~540MBYNN.
-15
CONTINUOUS OPERATION
AREA
PULL-DOWN
AREA
40
50
43
degr.C
ambient temperature
-20 -10 0 10 20
30
-20
-10
0
10
20
30
26
leaving
evaporator
water
temperature
degr.C
waterglycol
4-5
-30
16
39
33
27
Protect the water circuit against freezing by:
P Or heater tape (standard)
P Or filling up the system with a glycol solution
ESIE05-07.book Page 5 Wednesday, October 11, 2006 10:42 AM