Daikin EWTP400MBYN — обзор предупреждений и безопасностей для устранения неполадок [367/452]

Превью страниц Страница 367 / 452
Daikin EWAP110MBYNN [367/452] Overview of warnings
ESIE05-07 Overview of Fault Indications and Safeties
Part 3 – Troubleshooting 3–11
33
4
5
1
1.7 Overview of Warnings
In case of a warning, the unit can startup
Remark:
when a warning is activated, the unit keeps operating.
Warning Code&display Description
Safety possible
if unit is off?
1.Flow stopped
(Dual pump
safety)
UNIT WARNING
0AE: FLOW HAS STOPPED
Safety is activated if the digital input is open for
more then 5 second N
2. EEV battery
error C1
C1 WARNING
1A9: EEV BATTERY ERR
Battery problem if:
P Disconnected
P High internal resistance
P Down
Y
3. EEV battery
error C2
C2 WARNING
2A9: EEV BATTERY ERR
Same as for EEV battery error C1
Y
ESIE05-07.book Page 11 Wednesday, October 11, 2006 10:42 AM