Daikin EWTP400MBYN — данные тестирования и эксплуатации для систем отопления и охлаждения [432/452]

Превью страниц Страница 432 / 452
Daikin EWAD170MBYNN [432/452] Test run and operation data for ewtp110 170mbynn
Test Run and Operation Data ESIE05-07
4–26 Part 4 – Commissioning and Test Run
3
1
4
5
2.7 Test Run and Operation Data for EWTP110~170MBYNN
Pressures The table below contains the measurable pressures.
Temperatures The table below contains the measurable temperatures.
Voltages The table below contains the measurable voltages.
Currents The table below contains the currents and used fuses.
Measurement Value
Suction pressure
depending on working conditions
Discharge pressure
Maximum water pressure 10 bar
Measurement Value
Leaving water temperature evaporator
P Standard: 4 – 16°C
P With glycol: -10 – 16°C
Heat recovery inlet water temperature
condenser
depending on heat recovery setpoint
Outdoor temperature -15 – 43°C
Temperature difference at the air side 10 – 15°C
Temperature difference at the water side 3 – 8°C
Discharge temperature 80 – 120°C
Approach temperature evap.
(evap leaving water temp - sat. temp)
5 – 8°C (for MOW of 4°C)
for glycol units this can be > 8°C
Measurement Value
Power supply voltage Within ± 10% of the rated voltage
Phase imbalance Within ± 2% of the rated voltage
Control circuit voltage 230 V AC for main electromagnetic switches
24 V DC for the controllers
Unit Nominal current Maximum current Fuses
EWTP110MBYNN 70 A 95 A 3 x 125 gL A
EWTP140MBYNN 84 A 120 A
3 x 160 gL A
EWTP160MBYNN 104 A 135 A
EWTP200MBYNN 128 A 168 A 3 x 200 gL A
EWTP280MBYNN 180 A 232 A 3 x 250 gL A
EWTP340MBYNN 226 A 288 A 3 x 355 gL A
ESIE05-07.book Page 26 Wednesday, October 11, 2006 10:42 AM

Содержание

1124

Изучите данные о давлениях, температурах и токах для систем отопления и охлаждения. Узнайте о рабочих условиях и характеристиках для оптимальной работы оборудования.