Daikin EWTP400MBYN — функциональное описание цифрового контроллера для больших чиллеров [309/452]

Превью страниц Страница 309 / 452
Daikin EWAP460MBYN [309/452] What happens in case of an alarm or a warning
ESIE 05-07 The Digital Controller For Large chillers
Part 2 – Functional Description 2–113
3
2
4
5
1
4.4 What happens in Case of an Alarm or a Warning?
Introduction The units are equipped with four kinds of safety devices: unit safeties, circuit safeties, network safeties
and dual pump safety.
For a full list of all possible safeties reffer to overview of fault indications and safeties on page 3-9.
Overview safeties
Remark: How to view the safeties:
Press the
p key when the alarm is activated.
The appropriate safety screen with the basic information appears. Press the q key to see
the detailed information.
If more than one kind of safety is active (indicated by means of ^, v or ÷), use the
g and
h keys to consult them.
Unit safety Description
Safety possible
if unit is off?
1. Inlet Condenser sensor error +Err / -Err read-out by sensor Y
2. Inlet Evaporator sensor error +Err / -Err read-out by sensor Y
3. Reverse phase protector Safety is activated if digital input is closed Y
4. Flow stopped Safety is activated if digital input is longer
open then 5 seconds
N
Circuit safety Description
Safety possible
if unit is off?
1. Outlet Evaporator sensor error +Err / -Err read-out by sensor Y
2. General module safety Safety is activated if digital input is
opened
Y
3. Freeze-up module safety Safety is activated if digital input is closed Y
Network safety Description
Safety possible
if unit is off?
1. PCB Communication problems Safety is activated if network status is
not OK. (Only possible if a network of
different controllers exist)
Y
Dual pump safety Description
Safety possible
if unit is off?
1. Flow stopped Safety is activated if digital input is
longer open then 5 seconds
N
ESIE05-07.book Page 113 Wednesday, October 11, 2006 10:42 AM

Содержание

1124

Узнайте о функциональных возможностях цифрового контроллера для больших чиллеров, включая системы безопасности и управление аварийными ситуациями.