Pre-Test Run Checks ESIE05-07
4–8 Part 4 – Commissioning and Test Run
3
1
4
5
1.4 Water Pressure Drop through Evaporator: EWAP/EWTP110~160MBYNN
Water pressure
drop
The illustration below shows the water pressure drop through evaporator for
EWAP/EWTP110~160MBYNN.
Symbols The table below describes the symbols.
Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also
minimum and maximum allowed water flowrange. See "Technical Specifications:
EWAP110~540MBYNN" on page 1–4.
1
10
100
1000
100 100
0
Flow (l/min)
p (kPa)
1 2 3
= Filter + evaporator
= evaporator
Symbol Description
(1) For EWAP/EWTP110MBYNN
(2) For EWAP/EWTP140MBYNN
(3) For EWAP/EWTP160MBYNN
ESIE05-07.book Page 8 Wednesday, October 11, 2006 10:42 AM