Procedure to Protect Compressor in Case of Frozen Evaporator ESIE05-07
3–40 Part 3 – Troubleshooting
3
1
3
4
5
5.2 Procedure to Protect Compressor in Case of Frozen Evaporator
If water is detected in the compressor after a evaporator damage, the following procedure should be
executed within the first days.
1. Supply the compressor crank case heater.
2. Insulate the compressor from the rest of the refrigerant circuit. If there is no suction valve availa-
ble on the compressor, use a plate to close the suction of the compressor.
3. Open de oilplugs on the discharge and suction side to drain the oil and the water out of the
compressor.
4. Blow dry nitrogen through the compressor using the service ports on the HP and LP side of the
compressor.
5. Close the drain plugs and vacuum the compressor for a few hours while the crank case heater is
on.
6. If the vacuum oil becomes coloured (milky colour) replace the vacuum oil
7. Repeat step 6 each time the vacuum oil becomes milky.
8. After 4 hours break the vacuum using step 3.
9. Repeat step 5 till step 7 until the oil of the vacuum pump stays clear.
10. If the vacuum oil remains clear fill the compressor with the necessary compressor oil.
11. Charge the compressor with nitrogen.