Daikin EWTP400MBYN [287/452] Heat pressure control
ESIE05-07 The Functional Controller for DICN
Part 2 – Functional Description 2–91
3
2
4
5
1
3.8 Heat Pressure Control
MS Option = yes
(network unit)
MS Option = no
(standalone unit)
Low noise Mode Equal for all units Dedicated to this unit only
Changing Low noise
mode
If changed in one unit the value is
transferred to all units
Change in each unit.
Value is not transferred to other
units.
Active low noise by
schedule timer
Schedule timer in Master (see
remark)
Then activation is transferred to
all units.
Schedule timer (unit)
Dedicated to this unit only
Enable/disable low
noise by digital inputs
Select a changeable DI of each
unit.
Dedicated to this unit only
Select a changeable DI of each
unit
Dedicated to this unit only
Yes low noise Yes for all units in DICN Yes dedicated to this unit only
No low noise No for all units in DICN No dedicated to this unit only
Remark: Schedule timer is only available on master unit.