SiE-64 Troubleshooting
Troubleshooting 29
1.4 Photocatalytic Operation does not Activate.
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Photocatalytic operation does not activate during equipment operation (lamp does not light).
Supposed Causes Faulty lamp
Faulty transformer
Faulty PCB
Troubleshooting
YES
NO
Check power supply
voltage (A1P-X1A).
(for ACEF4AV1)
Check connector and
harness connection.
YES
YES
Correct connection
Replace control PCB (A1P)
Replace transformer
Replace sub power supply PCB.
(A6P)
Replace control P.C.B (A1P)
Faulty connection between X7A
(A1P) to CN1 (A4P)
Is connection
normal?
NO
(EF005)
Is voltage
between 220 to 240
VAC?
NO
Check power supply of
inverter PCB. (A4P-CN1)
Replace lamp or inverter PCB.
Check transformer
secondary voltage (sub
power supply A6P CN1).
YES
YES
Is voltage
higher than 12.5
VDC and lower
than 27
VDC?
NO
Is voltage
higher than 11.5
VDC and lower
than 12.5
VDC?
NO
For ACEF3AV1
A1P-X2A
For
ACEF3AV1
For ACEF3AV1
Check power supply of
control PCB (A1P) X7A
DC11.5~12.5V ?
For ACEF4AV1
Si-64.book Page 29 Monday, June 18, 2001 2:57 PM