Daikin RX36MY1 [105/255] Defective lubrication of compressor

Daikin RX10MTLE [105/255] Defective lubrication of compressor
SiE30-408 Malfunction Tree Analysis (FTA)
Troubleshooting 101
4.5 Defective Lubrication of Compressor
Load under
Short circuit
Dirty evaporator
Dirty air filter
Faulty control
Gas leakage
Faulty lubrication
of compressor
Oil volume
too small
Faulty oil
feed
Run out of oil
film
(Viscosity
low)
Oil return
volume low
Oil
discharge
volume high
Forming on
start-up
Backflow of
accumulated
refrigerant
ilution of oil
Oil
temperature
drop
Oil temperature
rise
Deterioration of
oil
Clogged oil return
path
Abnormal piping
length
Refrigerant
circulation low
Wet
operation
Clogged feed oil path
(Feed oil pump
failure)
Excessive
compressor
stop / start
Abnormal
overheat
operation
Moisture
mixed
Foreign matter
contamination
Clogged oil
return capillary
Clogged oil
separator
Refrigerant
charging low
Faulty
expansion
valve unit
Piping
connection with
the other way
Deformation of
piping
Faulty solenoid
valve unit
Foreign matters
caught
Faulty expansion
valve unit
Shortage of gas
Faulty operation
of expansion
valve
(Closing direction)
Excessive of
defrost time period
Faulty crank case
heater
Refrigerant over
charging
Refrigerant over
charging
Evaporator
airflow shortage
Clogged
refrigerant system
Liquid injection
solenoid valve
leakage
Excessive
compressor sta
rt /
stop
Faulty actuation
of expansion
valve (Opening
direction)
Moisture
contamination ·
Foreign matter
contamination
Faulty control
Faulty control
Wet
operation
Clogged
refrigerant filter

Содержание