Method of Troubleshooting SiE30-408
76 Troubleshooting
3.2.1 Thermistor
1. Symptoms with Thermistor Resistance Deviation
In Cooling with
Superheat
Degree Control
Code of Thermistors Detecting Various Temperatures
Units using R22, R407C Units using R410A
Tl (indoor liquid pipe temperature) Th2 R2T
Tg (indoor gas pipe temperature) Th3 R3T
Superheat degree (SH) = Tg-Tl
Tg-Tl decreases.
Indoor electronic EV closes.
Superheated degree (SH) = Tg-Tl
Tg-Tl increases.
Indoor electronic EV opens.
Superheat operation, cooling
capacity lowering (Freeze-up
protection cannot be detected.)
Wet operation (Freeze-up
protection can be applied
easily.)
Superheated degree (SH) = Tg-Tl
Tg-Tl increases.
Indoor electronic EV opens.
Wet operation
Superheat degree (SH) = Tg-Tl
Tg-Tl decreases.
Indoor electronic EV closes.
Indoor unit liquid pipe thermistor
· When the re
sistance deviates to smaller value.
(Higher temperature detected)
Indoor gas pipe thermistor
· When the resistance deviates to smaller value.
(Higher temperature detected)
· When the resistance deviates to larger value.
(Lower temperature detected)
· When the resistance deviates to larger value.
(Lower temperature detected)
Superhe
at operation,
cooling capacity lowering