Field Settings from Remote Controller 45
1.1.2 Settings of Group No. for Centralized Control System
In order to control with central controller or ON/OFF controller, settings of group No. to each
group using remote controller are necessary.
(Connect remote controller to indoor unit, which does not need remote controller, then remove
the remote controller after setting.)
Procedure 1 Turn on the power supply.
Turn on the power supply of indoor unit (+ System of rate control). (Setting is available only
with turning on the power supply.)
Check installation and electric wiring again before turning on the power supply.
(After all are displayed for turning the power, operation is occasionally not accepted,
displaying "88" for a period of about one minute.)
2 Put the system into setting mode.
While in normal mode, press and hold the button for a period of four seconds or more
to put the system into "Field Setting Mode".
3 Select mode No.
Select mode No. 00 using button.
4 Select group No.
Select group No. using the upper and lower button of .
(Group No. increases such as 1-00, 1-01 to 1-15, 2-00, to 4-15)
5 Determine group No.
Determine the content using button.
6 Return to normal mode.
Press button.
Note: Refer to installation manual for using simple remote controller.
Refer to each attached instruction manual for the settings of group No. of HRV or various kinds
of adapters (general purpose adapters)
Make the settings of group No. while the "group" in LCD is blinking. When no blinking, press the
button.
1-00
AIR CONDITIONER
00
SETTING
TEST
(VL044)
3
Mode No.
Field Set Mode
5
4
62
Group No.