Daikin RX36MY1 [215/255] For zone unified control the wiring procedure is the same as that for the individual control be sure to set the display output switch ss3 to zone

Daikin RX5MTLE [215/255] For zone unified control the wiring procedure is the same as that for the individual control be sure to set the display output switch ss3 to zone
SiE30-408 Adaptors for Connection of Air Conditioners
Appendix 211
For individual display: The wiring procedure is the same as that for the individual control.
Note The remote controller can be installed on indoor units to which the adapter PC board is not
directly connected.
3. For zone unified control: The wiring procedure is the same as that for the individual
control.
Be sure to set the display output switch (SS3) to Zone.
PC board ass'y
PC board ass'y
X18A
F1,F2P1,P2 P1,P2
SS
3
Remote controller
R/C
RS1
X18A
F1,F2
0
Z
I
Display output
Adapter PC board
CONTROL MODE
Adapter
PC board
16 units
at maximum
Do not set the control mode selector switch (RS1)
to Position 0. Not heeding this will not operate the
system due to the malfunction of setting.
DISPLAY OUTPUT
SS
3
Set the display output
switch (SS3) to
Individual.
DISPLAY OUTPUT
PC board ass'y PC board ass'y PC board ass'y
PC board ass'y
PC board ass'y
PC board ass'y PC board ass'y
Remote controller
Remote controller
Remote controller
X18AX18AX18A
F1,F2
P1,P2P1,P2P1,P2
X18AX18AX18A
P1,P2P1,P2P1,P2
P1,P2
F1,F2F1,F2
R/C
F1,F2F1,F2F1,F2
R/C
X18A
F1,F2
R/C
Note: For wire connections for centralized lines (F1, F2) to
the indoor units, connect wires to any one of indoor units in
one and the same group. (It isacceptable to connect wires to
any indoor unit other than indoor units to which the remote
controller is directly connected.)
(Wiringspecifications)
Types of wires...Sheathed vinyl cords or
cables (2 cores)
Size of wire...0.75 to 1.25 mm
2
Total length of wiring...1000 m at maximum
<Caution>
In order to prevent malfunctions, keep away
this wiring from the power lines.
DISPLAY OUTPUT
DISPLAY OUTPUT
16 units
at maximum
Adapter
PC board
16 units
at maximum
64 groups
at maximum