Control of Indoor Unit SiE30-408
28 Basic Information
4. Control of Indoor Unit
4.1 Thermostat-control
4.1.1 Operation Range of Remote Controller Thermostat
Room temperature is controlled by remote controller thermostat side and suction thermostat
(body-thermostat) on indoor unit side.
(However, when remote controller thermostat is set to "Not used " with field setting, the unit can
be controlled only by body-thermostat.)
Note: When the outdoor air (OA) mixed with indoor air is sucked, the room temperature may happen
to be out of the set temperature because the air temperature is out of the area of "operation
range of remote controller thermostat ". In such a case, install the remote controller thermostat
in the room where there is no influence of outdoor air.
Suction temperature (TH1)
12 14 16 18 20 22 24 26 2830 32 34
12 14 16 18 20 22 24 26 2830 32 34
20
22
24
26
28
30
32
34
16
15
18
20
22
24
26
28
30
Suction temperature (TH1)
Range in which body-thermostat can be used
Differential
In cooling operation
In heating operation
Switching point between remote controller
thermostat and body-thermostat
Range in which remote controller thermostat
can be used
Preset temperature
(TS)
Preset temperature
(TS)
Body-thermostat Body-thermostat
Body-thermostat Body-thermostat
Body-thermostat
Body-thermostat
Body-thermostat
Body-thermostat
Remote controller thermostat
Remote controller thermosta
t
Remote controller thermostat