Daikin RXYQ96PYDN [103/567] Procedure of check operation

Daikin RXYQ96PYDN [103/567] Procedure of check operation
Test Operation SiUS34-801A_b
88 VRVIII R-410A Heat Pump 60Hz
10.2.5.4Procedure of check operation
Perform the following Check Operation procedures or malfunction code [U3] will be displayed in
the remote controller and normal operation can not be carried out.
Check of shutoff valve opening
Check of miswiring
Judgment of piping length
Check of refrigerant overcharge
Note:
Check operation can not carried out at outdoor temp. less than 23°F.
Perform the check operation at a day or time that the outdoor temp. is 23°F or higher.
[Check Operation Procedure]
1. Close the Electrical Components Box lid and all front panels except as the side of the Electrical
Components Box and turn on the power to the outside unit and all connected BS, indoor units.
Be sure to turn the power on at least 6 hours before operation in order to have power running to
the crank case heater.
2. Make the onsite settings as needed using the push button (BS1-BS5) on the outside unit PC-
board (A1P) with the power on. See 10.2.6 Onsite Settings.
3. Perform the check operation following the Check Operation Method of the [Service Precautions]
label (lower) on the Electrical Components Box lid. See figure 32. The system operation for
about 40~60 minutes and automatically stops the check operation.
If the malfunction code is not displayed in the remote controller after the system stop, check
operation is completed. Normal operation will be possible after 5 minutes. If the malfunction
code is displayed in the remote controller, correct the malfunction displayed as [Remote
controller displays malfunction code] and perform the check operation again.
Note:
For interrupting the check operation, push RETURN button (BS3).
[Service Precaution] label (upper)
[Service Precaution] label (lower)
ELECTICAL COMPONENTS BOX (1) lid
fig. 32
< RXYQ144PTJU Only >
(Only RXYQ~PYDN and
RXYQ144PTJU)
ELECTRICAL COMPONENTS BOX (2) lid
[Service Precaution] label (upper)
Service Precaution] label (lower)
ELECTICAL COMPONENTS BOX (2) lid
ELECTICAL COMPONENTS BOX (1) lid