Daikin RXYQ96PYDN [215/567] 1 in case of multi outdoor unit system master unit it conducts the operation listed in the table above slave units operating units conduct the operation listed in the table above non operating units conduct the operation listed in the table above after the oil returning process non operating units stop while in preparation mode

Daikin RXYQ96PYDN [215/567] 1 in case of multi outdoor unit system master unit it conducts the operation listed in the table above slave units operating units conduct the operation listed in the table above non operating units conduct the operation listed in the table above after the oil returning process non operating units stop while in preparation mode
Special Control SiUS34-801A_b
200 VRVIII R-410A Heat Recovery 60Hz
The higher the compressor operating step No., the cumulative refrigerant oil consumption increases.
*1: In case of multi outdoor unit system:
Master unit: It conducts the operation listed in the table above.
Slave units: Operating units conduct the operation listed in the table above.
Non-operating units conduct the operation listed in the table above after the Oil Returning process. (Non-
operating units stop while in Preparation mode.)
Outdoor unit actuator Symbol
Elect. symbol
Oil return operation Operation after oil return
REYQ REMQ
Compressor 1
M1C M1C
52Hz+ON
(Subsequently, constant low
pressure control)
Maintain the number of
compressors that were used before
oil return operation)
52Hz+ON
(Subsequently, constant low
pressure control)
Maintain the number of
compressors that were used before
oil return operation)
Compressor 2 M2C M2C
Outdoor unit fan 1
M1F M1F
Cooling fan control Cooling fan control
Outdoor unit fan 2 M2F M2F
Four-way valve (for heat
exchanger selection)
20SA
Y2S
Y9S
Y3S OFF OFF
Four-way valve (for high-
and low-pressure gas
pipe selection)
20SB Y8S Y2S ON ON
Electronic expansion
valve (main)
EVM
Y1E
Y3E
Y1E 1375pls 1375pls
Electronic expansion
valve (subcooling)
EVT
Y2E
Y5E
Y3E SH control SH control
Electronic expansion
valve (refilling refrigerant)
EVJ Y4E Y2E 80pls 80pls
Solenoid valve (main
bypass)
SVE
Y5S
Y10S
Y6S ON ON
Solenoid valve (hot gas) SVP Y4S Y5S OFF OFF
Solenoid valve (liquid
pipe of refrigerant
regulator)
SVL Y3S Y4S 0pls 0pls
Solenoid valve (gas
discharge pipe of
refrigerant regulator)
SVG Y1S Y1S 0pls 0pls
Solenoid valve (drain pipe
of refrigerant regulator)
SVO Y7S Y7S 0pls 0pls
Solenoid valve (discharge
pipe of refrigerant
regulator)
SVT Y6S Y8S 0pls 0pls
End conditions
After a lapse of 5 min.
TsA - Te<41°F
After a lapse of 3 min.
Pe_min<41°F
Pc_max>526.35 psi
HTdmax>212°F
or
or