Daikin RXYQ96PYDN [462/567] Malfunction of transmission between optional controllers for centralized control

Daikin RXYQ96PYDN [462/567] Malfunction of transmission between optional controllers for centralized control
SiUS34-801A_b Troubleshooting (OP: Central Remote Controller)
Troubleshooting 447
4.2 M8 Malfunction of Transmission between Optional
Controllers for Centralized Control
Remote
Controller
Display
M8
Applicable
Models
Central remote controller Intelligent Touch Controller
Schedule timer
Method of
Malfunction
Detection
DIII-NET transmission data (The system will be automatically reset.)
Malfunction
Decision
Conditions
When no master controller is present at the time of the startup of slave controller.
When the connected centralized controller shows no response.
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control
Defect of PC board of optional controllers for centralized control