260 VRVIII R-410A Heat Recovery 60Hz
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
In setting mode 2, push the BS1 (MODE button) one time. Setting mode 2 is entered and
H1P lights.
During the time that setting mode 1 is displayed, In low noise operation and In demand
control are displayed.
2. Setting mode 2 (H1P on)
In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds. Setting mode 2
is entered and H1P lights.
Push the BS2 (SET button) several times and match the LED display with the Setting No. you
want.
Push the BS3 (RETURN button) one time, and the present setting content is displayed.
Push the BS2 (SET button) several times and match the LED display with the setting content
(as shown below) you want.
Push the BS3 (RETURN button) two times. Returns to .
Push the BS1 (MODE button) one time. Returns to the setting mode 1 and turns H1P off.