Daikin RXYQ96PYDN [402/567] Outdoor unit malfunction of high pressure sensor

Daikin RXYQ96PYDN [402/567] Outdoor unit malfunction of high pressure sensor
SiUS34-801A_b Troubleshooting by Indication on the Remote Controller
Troubleshooting 387
3.33 JA Outdoor Unit: Malfunction of High Pressure Sensor
Remote
Controller
Display
JA
Applicable
Models
RXYQ72P~240PYDN, PTJU
REYQ72P~240PYDN, PTJU
Method of
Malfunction
Detection
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Decision
Conditions
When the high pressure sensor is short circuit or open circuit.
(Not less than 611.9psi, or 1.45psi and below)
Supposed
Causes
Defect of high pressure sensor system
Connection of low pressure sensor with wrong connection.
Defect of outdoor unit PC board.
Defective connection of high pressure sensor