Daikin RXYQ96PYDN [481/567] Check 9 master slave unit setting table

Daikin RXYQ96PYDN [481/567] Check 9 master slave unit setting table
Troubleshooting (OP: Unified ON/OFF Controller) SiUS34-801A_b
466 Troubleshooting
[CHECK 9] Master-Slave Unit Setting Table
Combination of Intelligent Touch Controller and Central Remote Controller
CRC: Central remote controller <DCS302CA61>
Intelligent Touch controller: < >
The patterns marked with “” have nothing to do with those described in the list of Setting of master unit central setting connector.
#1 #2 #3 #4
Pattern
1-00~4-15
Master/
Slave
5-00~8-15
Master/
Slave
1-00~4-15
Master/
Slave
5-00~8-15
Master/
Slave
N CRC Master CRC Master CRC Slave CRC Slave
O CRC Master CRC Slave
P
Intelligent
Touch
controller
Master
Intelligent
Touch
controller
Slave
Q CRC Master
Intelligent
Touch
controller
Slave
R
Intelligent
Touch
controller
Master CRC Slave
S CRCMaster——————
T
Intelligent
Touch
controller
Master——————
#1 #2 #3 #4
Master
Slave
DCS601C51