Daikin RXYQ96PYDN [382/567] Outdoor unit malfunction of outdoor unit fan motor

Daikin RXYQ96PYDN [382/567] Outdoor unit malfunction of outdoor unit fan motor
SiUS34-801A_b Troubleshooting by Indication on the Remote Controller
Troubleshooting 367
3.19 E7 Outdoor Unit: Malfunction of Outdoor Unit Fan Motor
Remote
Controller
Display
E7
Applicable
Models
RXYQ72P~240PYDN, PTJU
REYQ72P~240PYDN, PTJU
Method of
Malfunction
Detection
Detect a malfunction based on the current value in the INVERTER PC board (as for motor 2,
current value in the fan PC board).
Detect a malfunction for the fan motor circuit based on the number of rotation detected by hole IC
during the fan motor operation.
Malfunction
Decision
Conditions
Overcurrent is detected for INVERTER PC board (A2P) or fan INVERTER PC board (A5P)
(System down is caused by 4 times of detection.)
In the condition of fan motor rotation, the number of rotation is below the fixed number for more
than 6 seconds. (System down is caused by 4 times of detection.)
Supposed
Causes
Failure of fan motor
Defective or connection error of the connectors/ harness between the fan motor and PC board
The fan cannot rotate due to any foreign substances entangled.
Clear condition: Continue normal operation for 5 minutes