Daikin RXYQ96PYDN [22/567] Differences from conventional models

Daikin RXYQ96PYDN [22/567] Differences from conventional models
SiUS34-801A_b Model Selection
General Information 7
Indoor Unit Capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (Btu/h).
The total capacity of connected indoor units can be within a range of 50 to 200% of the rated
capacity of the outdoor unit (rules apply).
In some models, it is not possible to connect the maximum number of connectable indoor units.
Select models so that the total capacity of connected indoor units conforms to the specification.
Unit Number and Capacity of Indoor Unit Connectable to BS Unit
Differences from Conventional Models
New refrigerant model code 07 type 09 type 12 type 18 type 24 type 30 type 36 type 48 type
Selecting model capacity
7,500
Btu/h
9,500
Btu/h
12,000
Btu/h
18,000
Btu/h
24,000
Btu/h
30,000
Btu/h
36,000
Btu/h
48,000
Btu/h
Equivalent output 0.6 ton 0.8 ton 1 ton 1.5 ton
2 ton
2.5 ton 3 ton 4 ton
Capacity of BS unit BSVQ36P BSVQ60P
Unit number of connectable
indoor unit
Five units or less Eight units or less
Total capacity of connectable
indoor unit
Less than 36000 Btu/h
36000 Btu/h or more, less than
60000 Btu/h
Connectable indoor unit Types 07M to 36M Types 07M to 48M
Item
Differences
Object New model (P Model) Conventional model (M Model)
Compressor Connection of equalizer oil pipe
NONE
(No particular changes in terms
of service)
YES
Workability
Equalizer oil pipe for multi-
outdoor-unit system
NONE YES
Procedure for calculating
refrigerant refilling quantity
Refilling quantity due to piping
length + Adjustment quantity
according to models of outdoor
units
Refilling quantity due to piping
length - Adjustment quantity
according to models of outdoor
units
Optional accessories
Branch pipe for outdoor unit
connection
Y branch
Type: BHFP26P90U
T branch
Type: BHFP26M90U