Daikin FTKE25BVMT [201/268] Heat pump units only

Daikin CDX50AVMA [201/268] Heat pump units only
Outdoor Units ED12-321A
196 Installation Manual
Night Quiet Mode setting
COOL/ HEAT mode lock <S15> (Heat Pump units only)
Night Quiet Mode
setting switch (SW5)
Service P-board
Jumper switch After removing
COOL mode (C)
HEAT mode (H)
5<C>3<H>1
Install the removed jumper switch as described below. This switch
will be needed to later disable this setting.
Note
If Night Quiet Mode is to be used, initial settings must be made when
the unit is installed.
Explain Night Quiet Mode, as described below, to the customer, and
confirm whether or not the customer wants to use Night Quiet Mode.
Use the S15 connector to set the unit to only cool or heat.
Setting to only cool (C): short-circuit pins 1 and 3 of the connector <S15>
Setting to only heat (H): short-circuit pins 3 and 5 of the connector <S15>
The following specifications apply to the connector housing and pins.
JST products Housing: VHR-5N
Pin: SVH-21T-1,1
Note that forced operation is also possible in COOL/HEAT mode.
About Night Quiet Mode
The Night Quiet Mode function reduces operating noise of the outdoor
unit at nighttime. This function is useful if the customer is worried about
the effects of the operating noise on the neighbors.
However, if Night Quiet Mode is running, cooling capacity will be saved.
Setting procedure
Remove the SW5 jumper switch.
Once the settings are complete, reset the power.