Daikin FDYM03FAV1C [160/410] Evl liquid pipe motorized valve opening restriction evl liquid pipe motorized valve

Daikin FDYM03FAV1C [160/410] Evl liquid pipe motorized valve opening restriction evl liquid pipe motorized valve
Si18-201 System control
Main Functions 147
3. EVL (liquid pipe motorized valve) opening restriction
EVL (liquid pipe motorized valve)
" ELV fully closed during normal heating
operation (after elapsed 30 sec or more)
" Other than the condition mentioned left
EVLMAX : 100 pulses
EVLMIN : 52 pulses
0 pulse
(M1042)
0 pulse
EVLMAX : 450 pulses
EVLMIN + EVLDP
(10)
EVLMIN : 12 pulses
Closed condition
(M1043)