Daikin FDXS25EAVMB [215/223] Jumper settings

Daikin FDXS35EAVMB [215/223] Jumper settings
SiBE07-724_B Field Settings
Trial Operation and Field Settings 205
A humidifier might cause dew jumping from the indoor unit outlet vent.
4. Cutting jumper sets the indoor fan tap to the highest position.
4.4 Jumper Settings
For the location of the jumper, refer to the following pages.
Indoor unit; page 21
Outdoor unit; page 23, 25, 27
Jumper Function When connected
(factory set)
When cut
JB
(on indoor unit PCB)
Fan speed setting
when compressor
stops for thermostat
OFF.
(effective only at
cooling operation)
Fan speed setting;
Remote controller
setting
Fan rpm is set to “0”
<Fan stop>
JC
(on indoor unit PCB)
Power failure
recovery function
Auto-restart The unit does not resume
operation after recovering from
a power failure. Timer ON/OFF
settings are cleared.
J5
(on outdoor unit
PCB)
Improvement of
defrost performance
Standard control Reinforced control
(ex. The frequency increases,
the duration time of defrost
lengthens.)