ED04-702 Electric Characteristics
Room Air Conditioners F-Series 35
11.Electric Characteristics
3D056403
3D054941
3D054943
REPRESENTATIVE UNIT COMBINATION POWER SUPPLY COMP OFM IFM
INDOOR UNIT OUTDOOR UNIT Hz-Volts VOLTAGE RANGE MCA MFA RHz RLA W FLA W FLA
FTKS50FVM RKS50FVM
50 - 220
MAX. 50Hz 264V
MIN. 50Hz 198V
19.75 20.0 67
6.7
53 0.19 43 0.12
50 - 230 6.4
50 - 240 6.1
60 - 220
MAX. 60Hz 253V
MIN. 60Hz 198V
6.7
60 - 230 6.4
FTKS60FVM RKS60FVM
50 - 220
MAX. 50Hz 264V
MIN. 50Hz 198V
19.75 20.0 84
8.7
53 0.20 43 0.14
50 - 230 8.3
50 - 240 7.9
60 - 220
MAX. 60Hz 253V
MIN. 60Hz 198V
8.7
60 - 230 8.3
FTKS71FVM RKS71FVM
50 - 220
MAX. 50Hz 264V
MIN. 50Hz 198V
19.75 20.0 60
11.0
53 0.28 43 0.16
50 - 230 10.5
50 - 240 10.1
60 - 220
MAX. 60Hz 253V
MIN. 60Hz 198V
11.0
60 - 230 10.5
FTXS50FVMA RXS50FVMA
50 - 220
MAX. 50Hz 264V
MIN. 50Hz 198V
19.75 20.0 67
6.7
53 0.32 43 0.17
50 - 230 6.4
50 - 240 6.1
60 - 220
MAX. 60Hz 253V
MIN. 60Hz 198V
6.7
60 - 230 6.4
FTXS60FVMA RXS60FVMA
50 - 220
MAX. 50Hz 264V
MIN. 50Hz 198V
19.75 20.0 84
8.7
53 0.39 43 0.18
50 - 230 8.3
50 - 240 7.9
60 - 220
MAX. 60Hz 253V
MIN. 60Hz 198V
8.7
60 - 230 8.3
FTXS71FVMA RXS71FVMA
50 - 220
MAX. 50Hz 264V
MIN. 50Hz 198V
19.75 20.0 56
10.3
66 0.40 43 0.19
50 - 230 9.9
50 - 240 9.4
60 - 220
MAX. 60Hz 253V
MIN. 60Hz 198V
10.3
60 - 230 9.9
SYMBOLS: NOTE:
MCA : MIN. CIRCUIT AMPS (A) 1. RLA is based on the following conditions.
Indoor temp. 27°CDB/19°CWB
Outdoor temp. 35°CDB.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. Be sure to install an earth leak detector. (One that can handle
higher harmonics.)
(This unit uses an inverter, which means that it must be used an
earth leak detector capable handling high harmonics in order to
prevent malfunctioning of the earth leak detector itself.
MFA : MAX. FUSE AMPS (A)
RLA : RATED LOAD AMPS (A)
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W : FAN MOTOR RATED OUTPUT (W)
RHz : RATED OPERATING FREQUENCY (Hz)