Troubleshooting - Outdoor Unit Related SiE18-201
252 Service Diagnosis
3.4.6 Power Transistor Check (Capacitor Voltage Check)
Check No.6 Power Transistor Check
Do not touch the charging unit for 10 minutes after turning the breaker off.
Even when touching the charging unit after 10 minutes, use a multiple meter to ensure that
the power supply voltage of power transistor is 50V or less.
Measure U,V,W either on terminals of control PC board on the substrate side or on the
compressor terminals.
Measure (+),(–) of the power transistor on (+) / (–) section of capacitor as shown in the figure
below.
If the resistance value is not normal, replace the control PC board.
Capacitor Voltage Check
Follow the below figure to measure the capacitor voltage with breaker kept ON, while take
enough care not to touch the charging unit .
ORANGE
(+)
BROWN
(–)
Capacitor (C1R)
(Q0005)
S102
H2P
Control PC Board
Power
transistor
line
S151
FU1
S140
Compressor's terminal
(U, V, W, N)
(Q0006)
Negative (–) terminal of tester
(positive (+) terminal for digital
type)
(+) of power
transistor
UVW (–) of power
transistor
UVW
Positive (+ terminal of tester
(negative (–) terminal for digital
type)
UVW (+) of power
transistor
UVW (–) of power
transistor
Normal resistance Several Kto
several M
Several K to
several M
Resistance for NG 0 0 to several 0 to several 0