Daikin FTX35JV1NB9 [90/162] Operation halt due to detection of input over current

Daikin FTK35JVET9 [90/162] Operation halt due to detection of input over current
Si04-115 Trouble shooting
Service Diagnosis 81
5.15 Operation Halt Due to Detection of Input Over Current
Remote
Controller
Display
E8
E8E8
E8
Outdoor unit LED
Display
A
5
55
5
Method of
Malfunction
Detection
Input over current is checked using the input current detected by the CT during compressor
operation.
Malfunction
Decision
Conditions
When the CT input remains above the value shown in the below table for 2.5 seconds during
compressor operation.
Table for constant
Supposed
Causes
"
Over current due to faulty compressor.
"
Over current due to faulty power transistor.
"
Over current due to faulty electrolytic capacitor of the main inverter circuit.
"
Over current due to faulty PCB.
"
Detection error due to faulty PCB.
"
Over current due to short-circuit.
Model Input current (A)
RK(X)25, 35 Series 10.0