Daikin EKPS076207 [166/216] Overview of daikin altherma c gas ec

Daikin EKPS076207 [166/216] Overview of daikin altherma c gas ec
166
Your guarantee of proper operation, especially in terms of the noise level of our heat generators, depends
on theuse of our own brand of ue-gas evacuation systems. All our condensing gas- and oil-red boilers
areoptimized and adjusted for this use.
All ue-gas ducts approved for condensing operation can be installed – an adapter may be needed
Treatment of condensate: neutralization is essential in all cases for Very High Energy Performance (condensing technology) oil-red boilers using o EL
standard oil. Neutralization may not be needed if low-sulfur fuel oil is used
Respect the local regulations
Requirements according to EN : Temperature class T , pressure class P, condensate consistence class W, corrosion-resistance class 
1-6 Variants for Daikin Altherma C Gas ECH
2
O
CA Air inlet (combustion)
FG Flue gas
RV Ventilation
a Variant for suction connection
(ue gas/concentric air inlet)
b Variant for partial suction connection
(ue gas/separated air inlet)
c Variant for connection dependent on ambient air
d Ventilated vertical ue ducts with re-resistance duration
of90minutes (30 minutes for low-rise buildings).
Respect the locally applicable standards!
e Ventilation opening (1 x 150 cm² or 2 x 75 cm²)
f Ventilation (150 cm²)
Overview of Daikin Altherma C Gas ECH
2
O
Connection variants for Very High Energy Performance (condensing technology)
Daikin Altherma C Gas ECH
2
O.