Panasonic CU-HE12NKE [104/110] Sensible capacity chart

Panasonic CU-HE12NKE [104/110] Sensible capacity chart
104
17.2 Sensible Capacity Chart
CU-HE9NKE CU-AE9NKE
230V Outdoor Temp. (°C)
30 35 40 46
Indoor wet
bulb temp.
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 2.48 1.88 0.42 2.32 1.80 0.45 2.16 1.73 0.48 1.96 1.65 0.52
19.0°C 2.50 0.46
19.5°C 2.72 1.97 0.42 2.55 1.89 0.46 2.37 1.82 0.49 2.15 1.73 0.53
22.0°C 2.97 2.04 0.43 2.77 1.96 0.47 2.58 1.89 0.50 2.35 1.81 0.54
CU-HE12NKE
230V Outdoor Temp. (°C)
30 35 40 46
Indoor wet
bulb temp.
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 3.47 2.63 0.76 3.24 2.52 0.82 3.02 2.43 0.87 2.74 2.30 0.94
19.0°C 3.50 0.83
19.5°C 3.81 2.76 0.77 3.56 2.65 0.83 3.31 2.55 0.89 3.01 2.43 0.96
22.0°C 4.15 2.86 0.79 3.88 2.75 0.85 3.61 2.65 0.91 3.28 2.53 0.98
TC - Total Cooling Capacity (kW)
SHC - Sensible Heat Capacity (kW)
IP - Input Power (kW)
Indoor 27°C/19°C
Outdoor 35°C/24°C