Panasonic CU-HE12NKE Сервис мануал онлайн [59/110] 626712

Panasonic CU-HE9NKE Сервис мануал онлайн [59/110] 626711
59
H59
ECO sensor
abnormality
Continuous for 70s
ECO sensor open or
short circuit
ECO sensor
ECO and Indoor PCB
H64
Outdoor high
pressure sensor
abnormality
Continuous for 1
minutes
High pressure sensor open
circuit during compressor
stop
High pressure sensor
Lead wire and connector
H70
Light sensor
abnormality
Continuous for 24
hours
Light sensor open or
short circuit
Light sensor
Indoor PCB
H97
Outdoor fan motor
mechanism lock
2 times happen
within 30 minutes
Outdoor fan motor lock or
feedback abnormal
Outdoor fan motor lead wire
and connector
Fan motor lock or block
H98
Indoor high pressure
protection
— —
Indoor high pressure
protection (Heating)
Check indoor heat exchanger
Air filter dirty
Air circulation short circuit
H99
Indoor operating unit
freeze protection
— —
Indoor freeze protection
(Cooling)
Check indoor heat exchanger
Air filter dirty
Air circulation short circuit
F11
4-way valve
switching
abnormality
4 times happen
within 30 minutes
4-way valve switching
abnormal
4-way valve
Lead wire and connector
F17
Indoor standby units
freezing abnormality
3 times happen
within 40 minutes
Wrong wiring and
connecting pipe, expansion
valve leakage, indoor heat
exchanger sensor open
circuit
Check indoor/outdoor
connection wire and pipe
Indoor heat exchanger sensor
lead wire and connector
Expansion valve lead wire and
connector
F90
Power factor
correction
(PFC) circuit
protection
4 times happen
within 10 minutes
Power factor correction
circuit abnormal
Outdoor PCB faulty
F91
Refrigeration cycle
abnormality
2 times happen
within 20 minutes
Refrigeration cycle
abnormal
Insufficient refrigerant or valve
close
F93
Compressor
abnormal revolution
4 times happen
within 20 minutes
Compressor abnormal
revolution
Power transistor module faulty
or compressor lock
F94
Compressor
discharge overshoot
protection
4 times happen
within 30 minutes
Compressor discharge
pressure overshoot
Check refrigeration system
F95
Outdoor cooling high
pressure protection
4 times happen
within 20 minutes
Cooling high pressure
protection
Check refrigeration system
Outdoor air circuit
F96
Power transistor
module overheating
protection
4 times happen
within 30 minutes
Power transistor module
overheat
PCB faulty
Outdoor air circuit (fan motor)
F97
Compressor
overheating
protection
3 times happen
within 30 minutes
— Compressor overheat
Insufficient refrigerant
F98
Total running current
protection
3 times happen
within 20 minutes
— Total current protection
Check refrigeration system
Power source or compressor
lock
F99
Outdoor direct
current (DC) peak
detection
Continuous
happen for 7 times
Power transistor module
current protection
Power transistor module faulty
or compressor lock