ioLogik W5300 Modbus/TCP Address Mapping
C-19
ioLogik W5312 Modbus Mapping
NOTE
For Modbus address
es of the ioLogik E1200 expansion modules attached to the ioLogik W5312, check the
ioAdmin
I/O Expansion tabs for details.
0xxxx Read/Write Coils (supports functions 1, 5, 15)
Reference Address Data Type Description
DIO Channels
00001 0x0000 1 bit CH0 DO Value 0: Off 1: On
00002 0x0001 1 bit CH1 DO Value 0: Off 1: On
00003 0x0002 1 bit CH2 DO Value 0: Off 1: On
00004 0x0003 1 bit CH3 DO Value 0: Off 1: On
00005 0x0004 1 bit CH4 DO Value 0: Off 1: On
00006 0x0005 1 bit CH5 DO Value 0: Off 1: On
00007 0x0006 1 bit CH6 DO Value 0: Off 1: On
00008 0x0007 1 bit CH7 DO Value 0: Off 1: On
00009 0x0008 1 bit CH8 DO Value 0: Off 1: On (DIO)
00010 0x0009 1 bit CH9 DO Value 0: Off 1: On (DIO)
00011 0x0010 1 bit CH10 DO Value 0: Off 1: On (DIO)
00012 0x0011 1 bit CH11 DO Value 0: Off 1: On (DIO)
00013 0x000C 1 bit CH0 DO Power On Value 0: Off 1: On
00014 0x000D 1 bit CH1 DO Power On Value 0: Off 1: On
00015 0x000E 1 bit CH2 DO Power On Value 0: Off 1: On
00016 0x000F 1 bit CH3 DO Power On Value 0: Off 1: On
00017 0x0010 1 bit CH4 DO Power On Value 0: Off 1: On
00018 0x0011 1 bit CH5 DO Power On Value 0: Off 1: On
00019 0x0012 1 bit CH6 DO Power On Value 0: Off 1: On
00020 0x0013 1 bit CH7 DO Power On Value 0: Off 1: On
00021 0x0014 1 bit CH8 DO Power On Value 0: Off 1: On (DIO)
00022 0x0015 1 bit CH9 DO Power On Value 0: Off 1: On (DIO)
00023 0x0016 1 bit CH10 DO Power On Value 0: Off 1: On (DIO)
00024 0x0017 1 bit CH11 DO Power On Value 0: Off 1: On (DIO)
00037 0x0024 1 bit CH0 DO Pulse Operate Status 0: Off 1: On
00038 0x0025 1 bit CH1 DO Pulse Operate Status 0: Off 1: On
00039 0x0026 1 bit CH2 DO Pulse Operate Status 0: Off 1: On
00040 0x0027 1 bit CH3 DO Pulse Operate Status 0: Off 1: On
00041 0x0028 1 bit CH4 DO Pulse Operate Status 0: Off 1: On
00042 0x0029 1 bit CH5 DO Pulse Operate Status 0: Off 1: On
00043 0x002A 1 bit CH6 DO Pulse Operate Status 0: Off 1: On
00044 0x002B 1 bit CH7 DO Pulse Operate Status 0: Off 1: On
00045 0x002C 1 bit CH8 DO Pulse Operate Status 0: Off 1: On (DIO)
00046 0x002D 1 bit CH9 DO Pulse Operate Status 0: Off 1: On (DIO)
00047 0x002E 1 bit CH10 DO Pulse Operate Status 0: Off 1: On (DIO)
00048 0x002F 1 bit CH11 DO Pulse Operate Status 0: Off 1: On (DIO)
00049 0x0030 1 bit CH0 DO PowerOn Pulse Operate Status 0: Off 1: On
00050 0x0031 1 bit CH1 DO PowerOn Pulse Operate Status 0: Off 1: On
00051 0x0032 1 bit CH2 DO PowerOn Pulse Operate Status 0: Off 1: On
00052 0x0033 1 bit CH3 DO PowerOn Pulse Operate Status 0: Off 1: On
00053 0x0034 1 bit CH4 DO PowerOn Pulse Operate Status 0: Off 1: On
00054 0x0035 1 bit CH5 DO PowerOn Pulse Operate Status 0: Off 1: On
Содержание
480- Iologik w5300 series user s manual
- Edition 9 november 2016
- Www moxa com product
- Iologik w5300 series user s manual
- Www moxa com support
- Trademarks
- Technical support contact information
- Disclaimer
- Copyright notice
- Table of contents
- Introduction
- Using active opc server to resolve dynamic ip addresses
- Iologik w5300 introduction
- Architecture
- Resolving dynamic private ip issues with ddns
- Iologik w5300 introduction
- Product features
- Overview
- Iologik w5300 introduction
- Appearance
- Physical dimensions unit mm
- Led indicators
- Iologik w5300 introduction
- Product specifications
- Product selection guide
- Package checklist
- Common specifications
- Physical characteristics
- Iologik w5300 introduction
- Environmental limits
- Warranty
- Standards and certifications
- Serial communication
- Power requirements
- Power requirements
- Mtbf mean time between failure
- Iologik w5340 w5340 t w5340 hspa w5340 hspa t
- Iologik w5312 w5312 t specifications
- Iologik w5300 introduction
- Inputs and outputs
- Digital output
- Digital input
- Analog input
- Iologik w5300 introduction
- Digital output
- Digital input
- Relay output
- Power requirements
- Mtbf mean time between failure
- Getting started
- Iologik w5300 getting started
- Installing the ioadmin utility
- Before testing
- Warning
- Laboratory testing
- Grounding the unit
- Connecting to ioadmin via ethernet
- Connecting to a power source
- Configuring the computer s ip address
- Attention
- Iologik w5300 getting started
- Activating ioadmin and connecting to the iologik
- Iologik w5300 getting started
- Iologik w5300 getting started
- Digital input dry contact
- Connecting i o devices
- Configuring digital i o channels
- Analog input
- Relay output
- Iologik w5300 getting started
- Digital output sink type
- Digital input wet contact connect to pnp type sensor
- Digital input wet contact connect to npn type sensor
- Testing i o devices
- Iologik w5300 getting started
- Attention
- Din rail wall mounting
- Attention
- Iologik w5300 getting started
- Installing removing sim and sd cards
- Iologik w5300 getting started
- Connecting the iologik w5300 to a cellular network
- Iologik w5300 getting started
- Installing aopc on a host with a static ip address
- Detailed instructions
- Iologik w5300 getting started
- Using ioadmin to import export a device configuration
- Import system config
- Import export a configuration file
- Export system config
- Attention
- The ioadmin utility
- Device management list
- Configuration file
- System requirements
- Remote management
- On line wiring guide
- Key features
- Using the ioadmin utility
- The ioadmin utility window
- Menu bar file
- Iologik w5300 the ioadmin utility
- Ioadmin menu bar
- Menu bar system
- Iologik w5300 the ioadmin utility
- Iologik w5300 the ioadmin utility
- Menu bar sort
- Iologik w5300 the ioadmin utility
- The wiring guide
- Iologik w5300 the ioadmin utility
- Sorting views
- Iologik w5300 the ioadmin utility
- Ioadmin quick link buttons
- Auto scan iologik devices
- Iologik w5300 the ioadmin utility
- Ioadmin navigation panel
- Basic functions add connect and disconnect
- Advanced functions delete restart reset import export config
- Main window
- Iologik w5300 the ioadmin utility
- I o configuration panel general
- Server settings panel general
- Server info panel
- Iologik w5300 the ioadmin utility
- Iologik w5300 the ioadmin utility
- Ioadmin status bar
- Synchronization rate status bar
- Message monitor panel general
- The server settings panel
- Iologik w5300 the ioadmin utility
- Ioadmin configuration panels
- Attention
- The lan settings panel
- Modbus tcp alive check timeout settings
- Ip settings
- Iologik w5300 the ioadmin utility
- Dns settings
- The i o configuration panel
- Snmp settings
- Configuring ai channels
- Two scaling methods slope formula and slope intercept
- Iologik w5300 the ioadmin utility
- Iologik w5300 the ioadmin utility
- Configuring virtual channels
- Iologik w5300 the ioadmin utility
- Iologik w5300 the ioadmin utility
- Configuring digital input channels
- Configuring digital i o channels
- Iologik w5300 the ioadmin utility
- Counter scaling
- Iologik w5300 the ioadmin utility
- Configuring digital output relay output channels
- Attention
- Relay count monitoring
- Iologik w5300 the ioadmin utility
- Testing di and do channels
- Iologik w5300 the ioadmin utility
- Attention
- The i o expansion panel
- Iologik w5300 the ioadmin utility
- Alias name
- Iologik w5300 the ioadmin utility
- Attention
- Iologik w5300 the ioadmin utility
- I o expansion step by step
- Iologik w5300 the ioadmin utility
- The active tags panel
- Iologik w5300 the ioadmin utility
- Iologik w5300 the ioadmin utility
- Active opc redundancy mode
- Read write privilege
- Iologik w5300 the ioadmin utility
- Heartbeat interval
- Active tags
- Iologik w5300 the ioadmin utility
- Attention
- The cellular settings panel
- Iologik w5300 the ioadmin utility
- Dial up setting
- Operation mode
- Iologik w5300 the ioadmin utility
- Caller ids
- Iologik w5300 the ioadmin utility
- Ddns settings
- Port forwarding
- Iologik w5300 the ioadmin utility
- Vpn settings panel iologik w5340 hspa t only
- Iologik w5300 the ioadmin utility
- Iologik ipsec vpn specifications
- Example gateway to gateway connection between iologik and ipsec servers
- What are virtual private networks vpns
- Manual key esp
- Iologik w5300 the ioadmin utility
- Ioadmin vpn settings tab
- General settings
- Local identify
- Isakmp psk
- Iologik w5300 the ioadmin utility
- Vpn system log events and error codes
- Isakmp phase 2
- Isakmp phase 1
- Iologik w5300 the ioadmin utility
- Advanced settings
- Iologik w5300 the ioadmin utility
- Cellular reconnection
- Iologik w5300 the ioadmin utility
- Op mode
- Meter sensor
- Network statistics
- Iologik w5300 the ioadmin utility
- Attention
- Watchdog panel
- Iologik w5300 the ioadmin utility
- Iologik w5300 the ioadmin utility
- Click go logic panel
- Attention
- Click go logic
- Iologik w5300 click go logic
- Iii start working with the logic
- Ii getting started
- I overview
- Click go function comparison table by product line
- To get a quick start
- Overview
- Iologik w5300 click go logic
- Features
- Click go logic basics
- Working with the rules
- Click go development process
- Attention
- I o configuration
- Digital input mode selection
- Configurable dio channel mode selection
- Attention
- Iologik w5300 click go logic
- Digital output mode selection
- Attention
- Alias configuration
- Iologik w5300 click go logic
- Analog input mode selection
- Testing the i o channels
- Iologik w5300 click go logic
- Attention
- Timer settings
- Iologik w5300 click go logic
- Internal register integer settings
- Defining global variables
- Snmp trap server
- Iologik w5300 click go logic
- E mail server
- Iologik w5300 click go logic
- Sms phone book
- Iologik w5300 click go logic
- Active message server
- Working off working days
- Iologik w5300 click go logic
- Ftp settings
- Iologik w5300 click go logic
- Data logging profile list
- Iologik w5300 click go logic
- Working with logic
- Iologik w5300 click go logic
- Internal register float settings
- Click go logic basics
- Iologik w5300 click go logic
- If a then b else c
- Iologik w5300 click go logic
- If then else conditionals
- Iologik w5300 click go logic
- Di digital input
- Iologik w5300 click go logic
- Counter
- Ai analog input
- Virtual channel
- Relay counter
- Iologik w5300 click go logic
- Iologik w5300 click go logic
- Internal register integer
- Schedule
- Iologik w5300 click go logic
- Expansion module connection fail
- System start up
- More information about repeat interval vs edge detection
- Iologik w5300 click go logic
- Iologik w5300 click go logic
- Iologik w5300 click go logic
- Then else actions
- Iologik w5300 click go logic
- Counter
- Pulse output
- Iologik w5300 click go logic
- Relay counts
- Iologik w5300 click go logic
- Iologik w5300 click go logic
- Internal register integer
- Snmp trap
- Iologik w5300 click go logic
- Attention
- Active message
- Iologik w5300 click go logic
- Short message service
- Iologik w5300 click go logic
- Iologik w5300 click go logic
- Ftp service
- Data log start stop
- Upload restart and run
- Iologik w5300 click go logic
- Activating the rule set
- Rule set management bar
- Iologik w5300 click go logic
- Import export configuration
- Planning and assistance
- Known issues of cellular monitoring systems
- Known issue 3 unexpected disconnection from cellular networks carriers
- Known issue 2 low bandwidth and slow response time
- Known issue 1 dynamic or private ip over a cellular network
- Iologik w5300 planning and assistance
- Active opc server with a static ip address
- Known issue 4 large power consumption when attached to base stations
- Iologik w5300 planning and assistance
- Using ioadmin to perform simple data monitoring from a remote site
- Iologik w5300 planning and assistance
- Cellular remote i o architecture
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Expanding input output channels
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Using modbus tcp protocol with your program
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Using the counter to get meter readings and statistics
- Iologik w5300 planning and assistance
- Record your i o data in the data log file
- Log profile creation
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Log file upload with ftp
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Environment
- Connecting to a scada system
- Connecting a modbus rtu serial device attached to the iologik over a cellular network
- Setup procedure
- Iologik w5300 planning and assistance
- Diagram
- Updating serial tags to scada system with active opc server over a cellular network
- Setup procedure
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Setup procedure
- Iologik w5300 planning and assistance
- Handling front end events and alarms
- Sms escalation and acknowledgement
- Setup procedure
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Sms commands for monitoring and control
- Setup procedure
- Iologik w5300 planning and assistance
- Iologik w5300 planning and assistance
- Enabling the power saving function and secure wake on call
- Setup procedure
- Setup procedure
- Iologik w5300 planning and assistance
- Enabling ethernet and cellular redundancy
- Pin outs and cable wiring
- Pinouts
- Iologik w5300 pin outs and cable wiring
- Cn3 rj 45 ethernet connector
- Cn2 db9 male rs 232 connector
- Cn1 sma cellular antenna connector
- Tb3 5 pin 4 wire 2 wire rs 422 485 terminal block
- Tb2 i o terminal block w5340
- Tb1 power input terminal block
- Iologik w5300 pin outs and cable wiring
- Digital input dry contact
- Cable wiring
- Tb2 i o terminal block w5312
- Iologik w5300 pin outs and cable wiring
- Digital input wet contact
- Relay output
- Iologik w5300 pin outs and cable wiring
- Digital output sink mode
- Attention
- Analog input
- Sms commands
- System information commands
- Sms command table
- Sms command syntax
- Example
- Details
- Iologik w5300 sms commands
- Example
- Local i o commands
- Iologik w5300 sms commands
- Expansion i o commands
- Optional commands
- Iologik w5300 sms commands
- Internal registers integer
- Example
- Details
- Modbus tcp address mapping
- Xxxx read write coils support functions 1 5 15
- Iologik w5340 and iologik w5340 hspa modbus mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Xxxx read only coils supports function 2
- Xxxx read only registers supports function 4
- Iologik w5300 modbus tcp address mapping
- Xxxx read write registers supports functions 3 6 16
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Xxxx write registers supports function 8
- Iologik w5300 modbus tcp address mapping
- Xxxx read write coils supports functions 1 5 15
- Iologik w5312 modbus mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Xxxx read only registers supports function 4
- Xxxx read only coils supports function 2
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Xxxx read write registers supports functions 3 6 16
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Iologik w5300 modbus tcp address mapping
- Xxxx write registers supports function 8
- Iologik w5300 modbus tcp address mapping
- Snmp agents with mib ii rs 232 like groups
- Rfc1213 mib ii supported snmp variables
- Iologik w5300 snmp agents with mib ii rs 232 like groups
- Iologik w5340 w5340 hspa
- Iologik w5300 snmp agents with mib ii rs 232 like groups
- Private mib file and snmp variables
- Iologik w5300 snmp agents with mib ii rs 232 like groups
- Factory default settings
- Iologik w5300 network port usage
- Iologik w5300 factory default settings
- Troubleshooting the cellular i o connection
- Sim card settings
- Self checklist
- Problem description
- Remote client test
- Iologik w5300 troubleshooting the cellular i o connection
- Ioadmin
- Client test
- Cellular modem error codes
- Active opc server aopc
- How to set active opc to get better connection quality
- Which tcp ports should initial open
- Service delay time
Похожие устройства
-
Moxa ioLogik W5340-TБрошюра -
Moxa ioLogik W5340-TТехнические характеристики -
Moxa ioLogik W5340-TИнструкция по эксплуатации -
Moxa ioLogik W5340Брошюра -
Moxa ioLogik W5340Технические характеристики -
Moxa ioLogik W5340Инструкция по эксплуатации -
Moxa ioLogik W5312-TБрошюра -
Moxa ioLogik W5312-TТехнические характеристики -
Moxa ioLogik W5312Брошюра -
Moxa ioLogik W5312Технические характеристики -
Moxa ioLogik W5312Инструкция по эксплуатации -
Moxa ioLogik W5340-HSPA-TБрошюра