ioLogik W5300 The ioAdmin Utility
3-18
The ioLogik W5300 has 10 internal virtual channels to support front-end statistics functions like Maximum
Value (Max), Minimum Value (Min), Average Value, Accumulation, Instantaneous, and Incremental.
The data source is the real I/O channel, such as AI and DI counters, some of which need to be converted to the
appropriate time unit. The operation is illustrated below.
After double-clicking on a virtual channel a popup window will appear (see below). First select the physical
source I/O. There are three types: AI, Counter, and I/O via Expansion Modules.
Next, choose the statistics function and time interval. There are six functions: Max, Min, Average,
Accumulation, Instantaneous, and Incremental. The time unit can be set to minutes or hours, with a
maximum value of 1440.
For example, if you want to monitor the daily flow at a point in a pipeline, you can use a pulse output flow meter
where 1 pulse indicates 5 ml. We can set the virtual channel’s scaling function so that 1 tick of counter input
equals 5 ml. Next, we set the Accumulation flag, and configure the Time Interval to 24 hours. This will set
up the virtual channel to log the total water flow volume over a period of 24 hours.
NOTE
Virtual channels are required to
configure AI or counter channels. For c
ounter channels, configure the
Counter Scaling
on the I/O Configuration panel before setting other operations in the virtual channels.
Use Virtual Channel to get the value, such as Max, Min,
Average, Accumulation, Instantaneous, and Incremental
Scale the value to a new unit
(This step may be skipped.)
AI Data
Counter Value
Display in
ioAdmin
Update to
AOPC