3-16
Alias Name (right figure, below) lets users configure the alias of an AI channel. The alias can be monitored by
the ioAdmin utility, or can be queried using either a user-defined program based on the Moxa MXIO library, or
a standard Modbus/TCP protocol.
Users can increase the sampling rate on devices using one channel by disabling the unused AI channel by
un-checking the Enable Channel checkbox, in the upper left corner of the window.
Enabling Auto Scaling will linearly convert the actual current or voltage value into other user defined units,
such as percentage or ppm (parts per million)
Two scaling methods: slope formula, and slope-intercept
Auto Scaling with the point-slope formula can help to eliminate high- and low-end extremes. For example,
if 17 mA represents the highest allowable temperature, then it is not necessary to allow higher temperature
values. You may then cut off any values beyond 17 mA and convert those to a proprietary danger level, such
as Level 5.