Moxa ioLogik W5312-T [91/194] Di digital input

Moxa ioLogik W5312 [91/194] Di digital input
ioLogik W5300 Click&Go Logic
4-19
IF conditions may be defined as follows:
IF Conditions Operators Remark
DI ON, OFF, ON to OFF, OFF to ON, Change DI-x represents the channel number
Counter =, >, <, >=, <=, Change Counter-x represents the channel number.
Max Counter Value: 4,294,967,295
AI =, >, <, >=, <= AI-x represents the number of the channel.
Max Value: Depends on the analog modes or
the result of scaling. Internal Register(Float)
can be used as the comparison or throughput
setting controlled by remote SCADA or a
Modbus/TCP program.
Relay =, >, <, >=, <= CurRelayCNT-x represents the current relay
counts for the channel.
Max Value: 4,294,967,295
Internal Register
= Reg-x represents the number of the
internal
register.
x = 00 to 23 / Trigger Value: 0 to 255
Timer TIMEOUT Timer-x, x = 00 to 23
Max value: 4,294,967,295 seconds
Schedule Time, Range and Recurrence
Expansion
Module
Connection
Failure
0, 1
Virtual Channel =, >, <, >=, <= VC-x represents the channel number
System Start up N/A Activate when the system is starting up at
System Start
NOTE
The following IF Conditions are only supported
by the ioLogik W5300: Expansion Module Connection
Failure
, Virtual Channel, and System Start-up.
DI: Digital Input
DI refers to the status of a digital input channel. Edge detection may be used to further define the electrical
requirements for signaling. For example, the condition DI-0=OFF is satisfied for as long as DI-0 remains off.
The condition DI-0=ON to OFF, however, is only satisfied the instant the DI-0 turns off. The transition of the
status change can also be handled using the Change operator, so that actions are triggered both for
ON-to-OFF and OFF-to-ON transitions.
Scroll to select DI and click on the property ( ) button to enter the DI Settings window.