Moxa ioLogik W5312-T [99/194] Counter

Moxa ioLogik W5312-T [99/194] Counter
ioLogik W5300 Click&Go Logic
4-27
If Conditions
Result of
OR Logic
Trigger of
Then Actions
Trigger of
ELSE Actions
A1 A2 A3
0 0 0 0 NO YES
0 0 1 1 YES NO
0 1 0 1 YES NO
0 1 1 1 YES NO
1 0 0 1 YES NO
1 0 1 1 YES NO
1 1 0 1 YES NO
1 1 1 1 YES NO
THEN/ELSE actions can be specified as follows:
THEN/ELSE Actions Operators Remark
Counter RESET Counter-x represents the number of the Event Counter channel
DO ON, OFF DO-[X] represents the number of the channel.
Pulse Output STOP, START Pulse Output-[X] represents the number of the channel
AO For ioLogik E1241 expansion
Relay Output RESET ResetCNT-[X] represents the number of the relay channel.
Internal Register Reg-x represents the number of the internal register.
x = 00 to 23 / Trigger Value: 0 to 255
Timer STOP, START,
RESTART
Timer-x, x = 00 to 23
Max value: 4,294,967,295 seconds
SNMP Trap I/O Status Bindings: 3 sets
Active Message ID / Source IP Unicode supported
e-Mail Create the contents of the email
Short Message Service Select recipients from the phone book, define the content, and
configure the escalation
Data Log Start/Stop Start, Stop Select which profile to start or stop
FTP Service Select which profile and FTP server to upload the log file
NOTE
T
he following THEN Actions are only supported by the ioLogik W5300: Short Message Service, Data Log
Start/Stop
, and FTP Service.
Counter
In this THEN/ELSE action, the only operator for the Counter function is RESET, which clears the counts of an
Event Counter channel. This function is often used in a charging system to clear the readings of a meter. Select
the THEN/ELSE action to Counter and click on the property button ( ) to enter the Counter Settings
window.