Moxa ioLogik E2212-T [110/263] Ai channels

Moxa ioLogik E2210 [110/263] Ai channels
ioLogik E2200 Series Using the Web Console
5-8
AI Channels
On the AI Channels page, you can view the status of each AI (analog input) channel.
Click on a channel to see that channel’s configuration options. AO Channels can operate in different input
modes, such as ±10V, or 4-20mA. The Reset Min and Reset Max buttons will clear the minimum or maximum
values recorded and displayed in the ioAdmin main window.
Auto Scaling can also help to eliminate high or low end extremes. For example, if 17 mA represents a
dangerous high temperature situation, it will not be necessary to get a temperature that is even higher. In this
case, users can cut off values beyond 17 mA and convert it to a proprietary level of danger, such as Level 5.
Alias Name
Alias Name helps users configure the alias of a DI, DO, or AI channel, and define the logic value (0 or 1) of the
ON/OFF status.

Содержание

Скачать