Summer performances Size : RT4D 80
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 45.4 44.1 43.6 42.7 41.8 41.2
Compressors power input (kW) 10.1 11.3 11.7 12.5 13.4 13.9
26 °C / 19.5 °C
Cooling capacity (kW) 47.8 46.5 45.9 45.1 44.1 43.5
Compressors power input (kW) 10.2 11.4 11.9 12.7 13.5 14.1
29 °C / 22 °C
Cooling capacity (kW) 52.1 50.7 50.1 49.1 48.1 47.4
compressors power input (kW) 10.4 11.6 12.1 12.9 13.8 14.4
31 °C / 24 °C
Cooling capacity (kW) 55.6 54.1 53.5 52.5 51.4 50.7
Compressors power input (kW) 10.6 11.8 12.3 13.1 14 14.6
Winter performances Size : RT4D 80
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 31.8 33.4 35.6 38.2 42 45.2
Compressors power input (kW) 9.6 9.8 10 10.3 10.7 11.1
18 °C / 40 %
Heating capacity (kW) 31.9 33.5 35.7 38.2 42 45.1
Compressors power input (kW) 10 10.2 10.4 10.7 11.2 11.6
20 °C / 40 %
Heating capacity (kW) 32 33.6 35.7 38.2 42 45.1
Compressors power input (kW) 10.4 10.6 10.8 11.1 11.6 12.1
22 °C / 40 %
Heating capacity (kW) 32.1 33.7 35.8 38.3 42 45
Compressors power input (kW) 10.8 11 11.3 11.6 12.1 12.6
Summer performances Size : RT4D 80
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 48.6 47.2 46.7 45.7 44.8 44.1
Compressors power input (kW) 9.31 10.41 10.78 11.52 12.35 12.81
26 °C / 19.5 °C
Cooling capacity (kW) 51.2 49.8 49.2 48.3 47.2 46.6
Compressors power input (kW) 9.40 10.51 10.97 11.7 12.44 13.00
29 °C / 22 °C
Cooling capacity (kW) 55.8 54.3 53.7 52.6 51.5 50.8
Compressors power input (kW) 9.59 10.69 11.15 11.89 12.72 13.27
31 °C / 24 °C
Cooling capacity (kW) 59.5 57.9 57.3 56.2 55.0 54.3
Compressors power input (kW) 9.77 10.88 11.34 12.07 12.90 13.46
Winter performances Size : RT4D 80
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 33.22 34.89 37.18 39.90 43.87 47.21
Compressors power input (kW) 8.39 8.56 8.74 9.00 9.35 9.70
18 °C / 40 %
Heating capacity (kW) 33.32 34.99 37.29 39.90 43.87 47.11
Compressors power input (kW) 8.74 8.91 9.09 9.35 9.79 10.14
20 °C / 40 %
Heating capacity (kW) 33.42 35.10 37.29 39.90 43.87 47.11
Compressors power input (kW) 9.09 9.26 9.44 9.70 10.14 10.57
22 °C / 40 %
Heating capacity (kW) 33.53 35.20 37.39 40.00 43.87 47.00
Compressors power input (kW) 9.44 9.61 9.88 10.14 10.57 11.01
Units Performance Data - RT4D 80