Airwell RT4D 60 [33/56] Hot water coils performance data option continued

Airwell RT4D 60 [33/56] Hot water coils performance data option continued
Page 33
Number of rows : 3
RT4D 240
Nominal air flow = 24 000 m
3
/h
Water temperature in-out = 70 °C - 60 °C
Outdoor
temp. °C
Outdoor air
% volume
Supply
temp. °C
Heating
capacity
kW
Water flow
rate
m
3
/h.
Water
pressure
drop kPa
7
40%
44.3 220 19.4 17
3 42.1 239 21.1 20
-3 38.8 267 23.5 24
-7 36.5 285 25.1 27
RT4D 240
Nominal air flow = 24 000 m
3
/h.
Water temperature in-out = 60 °C - 50 °C
Outdoor
temp. °C
Outdoor air
% volume
Supply
temp. °C
Heating
capacity
kW
Water flow
rate
m
3
/h.
Water
pressure
drop kPa
7
40%
38.4 173 15.2 12
3 36.4 191 16.8 14
-3 33.2 220 19.3 17
-7 31 238 20.9 20
RT4D 180
Nominal air flow = 18 000 m
3
/h
Water temperature in-out = 70 °C - 60 °C
Outdoor
temp. °C
Outdoor air
% volume
Supply
temp. °C
Heating
capacity
kW
Water flow
rate
m
3
/h.
Water
pressure
drop kPa
7
40%
44.2 165 14.5 15
3 42 179 16 17
-3 38.7 200 17.6 21
-7 36.4 214 18.9 23
RT4D 180
Nominal air flow = 18 000 m
3
/h
Water temperature in-out = 60 °C - 50 °C
Outdoor
temp. °C
Outdoor air
% volume
Supply
temp. °C
Heating
capacity
kW
Water flow
rate
m
3
/h.
Water
pressure
drop kPa
7
40%
38.3 129 11.4 10
3 36.3 143 12.6 12
-3 33.1 164 14.5 15
-7 30.9 178 15.7 17
RT4D 280
Nominal air flow = 28 000 m
3
/h
Water temperature in-out = 70 °C - 60 °C
Outdoor
temp. °C
Outdoor air
% volume
Supply
temp. °C
Heating
capacity
kW
Water flow
rate
m
3
/h.
Water
pressure
drop kPa
7
40%
46.1 274 24.1 17
3 44 297 26.1 20
-3 40.8 331 29.2 24
-7 38.7 354 31.2 27
RT4D 280
Nominal air flow = 28 000 m
3
/h.
Water temperature in-out = 60 °C - 50 °C
Outdoor
temp. °C
Outdoor air
% volume
Supply
temp. °C
Heating
capacity
kW
Water flow
rate
m
3
/h.
Water
pressure
drop kPa
7
40%
39.9 215 18.9 11
3 37.9 238 20.9 14
-3 34.9 273 24 17
-7 32.8 296 26 20
RT4D 380
Nominal air flow = 38 000 m
3
/h
Water temperature in-out = 70 °C - 60 °C
Outdoor
temp. °C
Outdoor air
% volume
Supply
temp. °C
Heating
capacity
kW
Water flow
rate
m
3
/h.
Water
pressure
drop kPa
7
40%
42.9 331 29.2 17
3 40.7 360 31.7 20
-3 37.3 402 35.4 24
-7 34.9 430 37.9 27
RT4D 380
Nominal air flow = 38 000 m
3
/h
Water temperature in-out = 60 °C - 50 °C
Outdoor
temp. °C
Outdoor air
% volume
Supply
temp. °C
Heating
capacity
kW
Water flow
rate
m
3
/h.
Water
pressure
drop kPa
7
40%
37.3 260 22.8 11
3 35.2 288 25.3 14
-3 31.9 330 29 17
-7 29.6 359 31.5 20