Airwell RT4D 60 [26/56] Units performance data rt4d 280

Airwell RT4D 60 [26/56] Units performance data rt4d 280
Page 26
Summer performances Size : RT4D 280
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 148.60 143.9 142 138.9 135.7 133.5
Compressors power input (kW) 31.3 35.2 36.9 39.6 42.4 44.4
26 °C / 19.5 °C
Cooling capacity (kW) 156.5 151.5 149.4 146.2 142.8 140.4
Compressors power input (kW) 31.6 35.6 37.3 40 42.8 44.8
29 °C / 22 °C
Cooling capacity (kW) 170.1 164.7 162.4 158.9 154.3 151.9
compressors power input (kW) 32.2 36.2 37.9 40.6 43.5 45.4
31 °C / 24 °C
Cooling capacity (kW) 180.9 175.3 172.9 168.8 164.7 162
Compressors power input (kW) 32.5 36.5 38.2 40.9 43.8 45.8
Winter performances Size : RT4D 280
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 102.5 108.5 116.7 126.6 140.7 151.8
Compressors power input (kW) 29.7 30.3 31 31.9 33.3 34.4
18 °C / 40 %
Heating capacity (kW) 102.5 108.4 116.7 126.5 140.5 151.4
Compressors power input (kW) 31.1 31.6 32.4 33.4 34.9 36
20 °C / 40 %
Heating capacity (kW) 102.5 108.5 116.7 126.5 140.3 151.1
Compressors power input (kW) 32.5 33.1 33.9 34.9 36.4 37.7
22 °C / 40 %
Heating capacity (kW) 102.5 108.5 116.8 126.5 140.2 150.9
Compressors power input (kW) 33.9 34.6 35.4 36.5 38.1 39.4
Summer performances Size : RT4D 280
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 162.6 157.4 155.3 152.0 148.5 146.0
Compressors power input (kW) 31.14 35.02 36.72 39.40 42.19 44.18
26 °C / 19.5 °C
Cooling capacity (kW) 171.2 165.7 163.4 160 156.2 153.6
Compressors power input (kW) 31.44 35.42 37.11 39.8 42.59 44.58
29 °C / 22 °C
Cooling capacity (kW) 186.1 180.2 177.7 173.8 168.8 166.2
Compressors power input (kW) 32.04 36.02 37.71 40.40 43.28 45.17
31 °C / 24 °C
Cooling capacity (kW) 197.9 191.8 189.2 184.7 180.2 177.2
Compressors power input (kW) 32.34 36.32 38.01 40.70 43.58 45.57
Winter performances Size : RT4D 280
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 107.22 113.49 122.07 132.42 147.17 158.78
Compressors power input (kW) 27.65 28.21 28.86 29.70 31.01 32.03
18 °C / 40 %
Heating capacity (kW) 107.22 113.39 122.07 132.32 146.96 158.36
Compressors power input (kW) 28.96 29.42 30.17 31.10 32.50 33.52
20 °C / 40 %
Heating capacity (kW) 107.22 113.49 122.07 132.3 146.75 158.05
Compressors power input (kW) 30.26 30.82 31.56 32.5 33.89 35.10
22 °C / 40 %
Heating capacity (kW) 107.22 113.49 122.17 132.32 146.65 157.84
Compressors power input (kW) 31.56 32.22 32.96 33.99 35.47 36.69
Units Performance Data - RT4D 280