Summer performances Size : RT4D 240
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 153.9 148.9 146.7 143.1 139.2 137.0
Compressors power input (kW) 28.24 31.72 33.27 35.69 38.10 39.85
26 °C / 19.5 °C
Cooling capacity (kW) 162.0 156.7 154.5 150.7 146.7 144.3
Compressors power input (kW) 28.53 32.01 33.46 35.8 38.30 40.14
29 °C / 22 °C
Cooling capacity (kW) 175.5 169.4 166.9 163.2 159.2 156.6
compressors power input (kW) 28.92 32.50 34.04 36.46 38.97 40.81
31 °C / 24 °C
Cooling capacity (kW) 186.0 179.8 177.2 173.2 169.2 166.2
Compressors power input (kW) 29.30 32.98 34.53 36.94 39.56 41.39
Winter performances Size : RT4D 240
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 100.31 106.41 114.35 123.92 137.74 148.62
Compressors power input (kW) 24.25 24.69 25.22 25.93 26.99 27.79
18 °C / 40 %
Heating capacity (kW) 100.31 106.41 114.35 123.81 137.52 148.29
Compressors power input (kW) 25.31 25.75 26.37 27.08 28.23 29.12
20 °C / 40 %
Heating capacity (kW) 100.31 106.41 114.46 123.8 137.31 147.97
Compressors power input (kW) 26.46 26.99 27.52 28.4 29.47 30.44
22 °C / 40 %
Heating capacity (kW) 100.31 106.52 114.46 123.81 137.20 147.75
Compressors power input (kW) 27.61 28.05 28.76 29.56 30.80 31.86
Summer performances Size : RT4D 240
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 163.4 158.1 155.8 151.9 147.8 145.4
Compressors power input (kW) 28.10 31.57 33.11 35.51 37.92 39.65
26 °C / 19.5 °C
Cooling capacity (kW) 172.0 166.4 164.1 160.0 155.8 153.3
Compressors power input (kW) 28.39 31.86 33.30 35.6 38.11 39.94
29 °C / 22 °C
Cooling capacity (kW) 186.3 179.8 177.2 173.2 169.0 166.3
Compressors power input (kW) 28.78 32.34 33.88 36.28 38.79 40.62
31 °C / 24 °C
Cooling capacity (kW) 197.5 190.9 188.1 183.9 179.6 176.5
Compressors power input (kW) 29.16 32.82 34.36 36.77 39.36 41.19
Winter performances Size : RT4D 240
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 104.55 110.91 119.18 129.16 143.56 154.90
Compressors power input (kW) 22.89 23.31 23.81 24.48 25.48 26.23
18 °C / 40 %
Heating capacity (kW) 104.55 110.91 119.18 129.05 143.34 154.56
Compressors power input (kW) 23.89 24.31 24.90 25.56 26.65 27.49
20 °C / 40 %
Heating capacity (kW) 104.55 110.91 119.30 129.0 143.11 154.22
Compressors power input (kW) 24.98 25.48 25.98 26.8 27.82 28.74
22 °C / 40 %
Heating capacity (kW) 104.55 111.02 119.30 129.05 143.00 154.00
Compressors power input (kW) 26.07 26.48 27.15 27.90 29.07 30.08
Units Performance Data - RT4D 240 (continued)