Airwell RT4D 60 [27/56] Units performance data rt4d 280 continued

Airwell RT4D 60 [27/56] Units performance data rt4d 280 continued
Page 27
Summer performances Size : RT4D 280
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 170.3 164.9 162.7 159.2 155.5 153.0
Compressors power input (kW) 30.84 34.68 36.35 39.01 41.77 43.74
26 °C / 19.5 °C
Cooling capacity (kW) 179.3 173.6 171.2 167.5 163.6 160.9
Compressors power input (kW) 31.13 35.07 36.75 39.4 42.17 44.14
29 °C / 22 °C
Cooling capacity (kW) 194.9 188.7 186.1 182.1 176.8 174.1
compressors power input (kW) 31.72 35.67 37.34 40.00 42.86 44.73
31 °C / 24 °C
Cooling capacity (kW) 207.3 200.9 198.1 193.4 188.7 185.7
Compressors power input (kW) 32.02 35.96 37.64 40.30 43.15 45.12
Winter performances Size : RT4D 280
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 110.50 116.96 125.80 136.47 151.67 163.64
Compressors power input (kW) 26.47 27.01 27.63 28.43 29.68 30.66
18 °C / 40 %
Heating capacity (kW) 110.50 116.86 125.80 136.37 151.46 163.21
Compressors power input (kW) 27.72 28.16 28.88 29.77 31.11 32.09
20 °C / 40 %
Heating capacity (kW) 110.50 116.96 125.80 136.4 151.24 162.89
Compressors power input (kW) 28.97 29.50 30.21 31.1 32.44 33.60
22 °C / 40 %
Heating capacity (kW) 110.50 116.96 125.91 136.37 151.14 162.67
Compressors power input (kW) 30.21 30.84 31.55 32.53 33.96 35.12
Summer performances Size : RT4D 280
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 180.3 174.6 172.2 168.5 164.6 161.9
Compressors power input (kW) 30.45 34.24 35.89 38.52 41.25 43.19
26 °C / 19.5 °C
Cooling capacity (kW) 189.8 183.8 181.2 177.3 173.2 170.3
Compressors power input (kW) 30.74 34.63 36.28 38.9 41.63 43.58
29 °C / 22 °C
Cooling capacity (kW) 206.3 199.8 197.0 192.7 187.2 184.3
Compressors power input (kW) 31.32 35.21 36.87 39.49 42.32 44.16
31 °C / 24 °C
Cooling capacity (kW) 219.4 212.6 209.7 204.8 199.8 196.5
Compressors power input (kW) 31.61 35.51 37.16 39.79 42.61 44.55
Winter performances Size : RT4D 280
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 115.01 121.74 130.94 142.05 157.87 170.32
Compressors power input (kW) 25.02 25.53 26.12 26.87 28.05 28.98
18 °C / 40 %
Heating capacity (kW) 115.01 121.62 130.94 141.93 157.64 169.87
Compressors power input (kW) 26.20 26.62 27.30 28.14 29.40 30.33
20 °C / 40 %
Heating capacity (kW) 115.01 121.74 130.94 141.9 157.42 169.53
Compressors power input (kW) 27.38 27.89 28.56 29.4 30.67 31.76
22 °C / 40 %
Heating capacity (kW) 115.01 121.74 131.05 141.93 157.30 169.31
Compressors power input (kW) 28.56 29.15 29.82 30.75 32.10 33.19
Units Performance Data - RT4D 280 (continued)

Содержание