Airwell RT4D 60 [17/56] Units performance data rt4d 80 continued

Airwell RT4D 60 [17/56] Units performance data rt4d 80 continued
Page 17
Summer performances Size : RT4D 80
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 50.7 49.3 48.7 47.7 46.7 46.0
Compressors power input (kW) 9.23 10.32 10.69 11.42 12.24 12.70
26 °C / 19.5 °C
Cooling capacity (kW) 53.4 51.9 51.3 50.4 49.3 48.6
Compressors power input (kW) 9.32 10.41 10.87 11.60 12.33 12.88
29 °C / 22 °C
Cooling capacity (kW) 58.2 56.6 56.0 54.8 53.7 52.9
compressors power input (kW) 9.50 10.60 11.05 11.78 12.61 13.15
31 °C / 24 °C
Cooling capacity (kW) 62.1 60.4 59.8 58.6 57.4 56.6
Compressors power input (kW) 9.68 10.78 11.23 11.97 12.79 13.34
Winter performances Size : RT4D 80
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 34.22 35.94 38.31 41.10 45.19 48.64
Compressors power input (kW) 8.05 8.21 8.38 8.63 8.97 9.30
18 °C / 40 %
Heating capacity (kW) 34.32 36.05 38.41 41.10 45.19 48.53
Compressors power input (kW) 8.38 8.55 8.72 8.97 9.39 9.72
20 °C / 40 %
Heating capacity (kW) 34.43 36.15 38.41 41.10 45.19 48.53
Compressors power input (kW) 8.72 8.89 9.05 9.30 9.72 10.14
22 °C / 40 %
Heating capacity (kW) 34.54 36.26 38.52 41.21 45.19 48.42
Compressors power input (kW) 9.05 9.22 9.47 9.72 10.14 10.56
Summer performances Size : RT4D 80
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 54.0 52.5 51.9 50.8 49.7 49.0
Compressors power input (kW) 8.99 10.06 10.42 11.13 11.93 12.38
26 °C / 19.5 °C
Cooling capacity (kW) 56.9 55.3 54.6 53.7 52.5 51.8
Compressors power input (kW) 9.08 10.15 10.60 11.3 12.02 12.56
29 °C / 22 °C
Cooling capacity (kW) 62.0 60.3 59.6 58.4 57.2 56.4
Compressors power input (kW) 9.26 10.33 10.77 11.49 12.29 12.82
31 °C / 24 °C
Cooling capacity (kW) 66.2 64.4 63.7 62.5 61.2 60.3
Compressors power input (kW) 9.44 10.51 10.95 11.67 12.47 13.00
Winter performances Size : RT4D 80
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 35.46 37.24 39.69 42.59 46.83 50.40
Compressors power input (kW) 7.61 7.77 7.93 8.17 8.49 8.80
18 °C / 40 %
Heating capacity (kW) 35.57 37.35 39.81 42.59 46.83 50.29
Compressors power input (kW) 7.93 8.09 8.25 8.49 8.88 9.20
20 °C / 40 %
Heating capacity (kW) 35.68 37.46 39.81 42.6 46.83 50.29
Compressors power input (kW) 8.25 8.41 8.56 8.80 9.20 9.60
22 °C / 40 %
Heating capacity (kW) 35.79 37.58 39.92 42.70 46.83 50.18
Compressors power input (kW) 8.56 8.72 8.96 9.20 9.60 9.99
Units Performance Data - RT4D 80 (continued)