Airwell RT4D 60 [24/56] Units performance data rt4d 240

Airwell RT4D 60 [24/56] Units performance data rt4d 240
Page 24
Summer performances Size : RT4D 240
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 135.80 131.4 129.5 126.3 122.9 120.9
Compressors power input (kW) 29.2 32.8 34.4 36.9 39.4 41.2
26 °C / 19.5 °C
Cooling capacity (kW) 143 138.3 136.4 133 129.5 127.4
Compressors power input (kW) 29.5 33.1 34.6 37 39.6 41.5
29 °C / 22 °C
Cooling capacity (kW) 154.9 149.5 147.3 144 140.5 138.2
compressors power input (kW) 29.9 33.6 35.2 37.7 40.3 42.2
31 °C / 24 °C
Cooling capacity (kW) 164.2 158.7 156.4 152.9 149.3 146.7
Compressors power input (kW) 30.3 34.1 35.7 38.2 40.9 42.8
Winter performances Size : RT4D 240
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 92.2 97.8 105.1 113.9 126.6 136.6
Compressors power input (kW) 27.4 27.9 28.5 29.3 30.5 31.4
18 °C / 40 %
Heating capacity (kW) 92.2 97.8 105.1 113.8 126.4 136.3
Compressors power input (kW) 28.6 29.1 29.8 30.6 31.9 32.9
20 °C / 40 %
Heating capacity (kW) 92.2 97.8 105.2 113.8 126.2 136
Compressors power input (kW) 29.9 30.5 31.1 32.1 33.3 34.4
22 °C / 40 %
Heating capacity (kW) 92.2 97.9 105.2 113.8 126.1 135.8
Compressors power input (kW) 31.2 31.7 32.5 33.4 34.8 36
Summer performances Size : RT4D 240
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 147.2 142.4 140.4 136.9 133.2 131.1
Compressors power input (kW) 28.43 31.94 33.50 35.93 38.36 40.12
26 °C / 19.5 °C
Cooling capacity (kW) 155.0 149.9 147.9 144.2 140.4 138.1
Compressors power input (kW) 28.72 32.23 33.69 36.0 38.56 40.41
29 °C / 22 °C
Cooling capacity (kW) 167.9 162.1 159.7 156.1 152.3 149.8
Compressors power input (kW) 29.11 32.72 34.27 36.71 39.24 41.09
31 °C / 24 °C
Cooling capacity (kW) 178.0 172.0 169.5 165.7 161.8 159.0
Compressors power input (kW) 29.50 33.20 34.76 37.20 39.82 41.67
Winter performances Size : RT4D 240
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 97.18 103.08 110.78 120.05 133.44 143.98
Compressors power input (kW) 25.28 25.74 26.29 27.03 28.14 28.97
18 °C / 40 %
Heating capacity (kW) 97.18 103.08 110.78 119.95 133.23 143.66
Compressors power input (kW) 26.38 26.85 27.49 28.23 29.43 30.35
20 °C / 40 %
Heating capacity (kW) 97.18 103.08 110.88 120 133.01 143.34
Compressors power input (kW) 27.58 28.14 28.69 29.6 30.72 31.73
22 °C / 40 %
Heating capacity (kW) 97.18 103.19 110.88 119.95 132.91 143.13
Compressors power input (kW) 28.78 29.24 29.98 30.81 32.10 33.21
Units Performance Data - RT4D 240