Yaskawa CIMR-UU4A0034A [158/644] B1 operation mode selection

Yaskawa CIMR-UU4A0034A [158/644] B1 operation mode selection
5.2 b: Application
u
b1: Operation Mode Selection
n
b1-01: Frequency Reference Selection 1
Selects the frequency reference source 1 for the REMOTE mode.
Note:
1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator
LED on the digital operator will light and the STOP indicator will flash. However, the RUN indicator LED will light in zero speed
control when A1-02 is set to 3, 4, or 6.
2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.
No. Parameter Name Setting Range Default
b1-01 Frequency Reference Selection 1 0 to 4 1
Setting 0: Operator keypad
Using this setting, the frequency reference can be input by:
switching between the multi-speed references in the d1-oo parameters.
entering the frequency reference on the operator keypad.
Setting 1: Terminals (analog input terminals)
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in Table 5.5 for the input
used.
Table 5.5 Analog Input Settings for Frequency Reference Using Voltage Signals
Terminal Signal Level
Parameter Settings
Notes
Signal Level
Selection
Function Selection Gain Bias
A1
0 to 10 Vdc H3-01 = 0
H3-02 = 0
(Frequency Reference Bias)
H3-03 H3-04
-10 to +10 Vdc H3-01 = 1
A2
0 to 10 Vdc H3-09 = 0
H3-10 = 0
(Frequency Reference Bias)
H3-11 H3-12
Set DIP switch S1 on the
terminal board to “V” for
voltage input.
-10 to +10 Vdc H3-09 = 1
A3
0 to 10 Vdc H3-05 = 0
H3-06 = 0
(Frequency Reference Bias)
H3-07 H3-08
Set DIP switch S4 on the
terminal board to “AI”.
-10 to +10 Vdc H3-05 = 1
Drive
A1 Analog Input 1
0 to 10 V
AC Analog input common
2 k
+V
-V
10.5 V, 20 mA power supply
-10.5 V, 20 mA power supply
A2 Analog Input 2
A3 Analog Input 3
Drive
A1 Analog Input 1
AC Analog input common
+V
-V
10.5 V, 20 mA power supply
-10.5 V, 20 mA power supply
A2 Analog Input 2
A3 Analog Input 3
4 k
-10 to 10 V
OR
Figure 5.1 Setting the Frequency Reference as a Voltage Signal at Terminal A1
Use the wiring example shown in the figure above for any other analog input terminals. When using input A2 make sure DIP
switch S1 is set for voltage input.
Current Input
Input terminal A2 can accept a current input signal. Refer to Table 5.6 to set terminal A2 for current input.
5.2 b: Application
158
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual

Содержание

Похожие устройства

Скачать